Diagnostics and troubleshooting
Cerabar M, Deltapilot M
64
Hauser
10.2 Behavior of the current output in the event of an
error
The response of the current output to errors is defined by the following parameters:
Output fail mode (051)/(190)
Navigation
Setup → Extended setup → Current output → Output fail mode (051)/(190)
Expert → Output → Current output → Output fail mode (051)/(190)
Write permission
Operator/Maintenance/Expert
Description
Select Output fail mode. In the event of an alarm, the current and the bar graph assume
the current value specified with this parameter.
Selection
• Max. alarm: can be set from 21 to 23 mA
• Hold measured value: last measured value is held.
• Min: 3.6 mA
Factory setting
Max. alarm (22 mA)
10.3 Locking/unlocking operation
Once you have entered all the parameters, you can lock your entries against unauthorized
and undesired access.
Locked operation is indicated as follows:
• By the
symbol on the local display
• The parameters are grayed out in FieldCare and the handheld terminal, which means
they cannot be edited. Information displayed in the "" parameter.
Parameters which refer to how the display appears, e.g. "Language ", can still be altered.
The "Operator code" parameter is used to lock and unlock the device.
Operator code (021)
Write permission
Operators/Service engineers/Expert
Description
Use this function to enter a code to lock or unlock operation.
User entry
• To lock: Enter a number ≠ the release code (value range: 1 to 9999).
• To unlock: Enter the release code.
Note
The release code is "0" in the order configuration. Another release code can be defined in
the "Code definition" (023) parameter. If the user has forgotten the release code, the
release code can be visible by entering the number "5864".
Factory setting
0