Cerabar M
Hauser
27
P01-PMP4xxxx-17-xx-xx-xx-000
Wall and pipe-mounting PMP46/PMP48
The dimensions in brackets apply to housings with a raised cover (for optional display). Dimensions written in
italics apply to devices with an aluminum housing.
Oxygen applications
Oxygen and other gases can react explosively to oils, grease and plastics, such that, among other things, the
following precautions must be taken:
– All components of the system, such as measuring devices, must be cleaned in accordance with BAM
requirements (DIN 19247). (BAM = Federal Institute for Materials Research and Testing).
– Depending on the materials used, a certain maximum temperature and a maximum pressure must not be
exceeded in oxygen applications. The maximum temperature T
max
for oxygen applications is 60°C (+140°F).
The devices suitable for gaseous oxygen applications are listed in the following table, indicated by p
max
.
PWIS-free applications
Special cleaning of transmitter to remove paint-wetting impairment substances e.g. for use in paint shops
→
see Page 67 ff "Ordering information", feature 80 "Sensor seal".
Ultrapure gas applications
Hauser also provides devices which have been cleaned of oil and grease for special applications, such
as ultrapure gas. No special restrictions regarding the process conditions apply to these devices.
→
See also Page 68, PMC41: feature 80 "Sensor seal".
→
See also Page 73, PMP41: feature 80 "Seal; Fill fluid".
1
84.
5
187.6
60
.
3
8
1
119
.
5
26
99
(
11
9
)
108
(122)
7
0
102
.
5
16
7.
5
170.7
108
(122)
99
(
11
9
)
26
3
Order code for devices cleaned for oxygen
applications
p
max
for oxygen applications
PMC41 – * ** ** * * * ** 6,
for devices with sensors, nominal value < 10 bar
Overpressure limit (OPL) of sensor
1
1)
→
See Page 67 ff "Ordering information", feature 30 "Sensor range; MWP; OPL".
PMC41 – * ** ** * * * ** 6,
for devices with sensors, nominal value
≥
10 bar
30 bar
PMP41 – * ** ** * * * ** C,
for devices with sensors, nominal value < 40 bar
Overpressure limit (OPL) of sensor
1
PMP41 – * ** ** * * * ** C,
for devices with sensors, nominal value
≥
40 bar
160 bar
PMP46 – * ** ** * * * ** N
Depends on the element of the selected components which has the
lowest pressure rating: overpressure limit (OPL) of sensor
1
or process
connection (1.5 x PN)
PMP48 – * ** ** * * * ** N *
Depends on the element of the selected components which has the
lowest pressure rating: overpressure limit (OPL) of sensor
1
, process
connection (1.5 x PN) or fill fluid (160 bar)