Entering from the programming mode to the run mode:
If no key is pressed within 20 seconds during programming mode, the data is stored automatically and the run mode is entered.
Alternatively, the same function occurs first pressing key and then pressing keys together.
Before starting sef-tune
procedure, be sure
A.tun
parameter is
YES
in the
SECU
menu.
S.Str.
run
SET
CSET
SET
CSET
SET
CSET
S.Str.
run
SECU.
ASET
S.cod.
0
A.Con.
P.yES
A.ALr.
P.yES
A.CNF.
P.yES
A.tun.
yES
ASET
S.cod.
=
code.
It should be 666.
Security menu access
A.Con.
=
CoN.o
access level code.
nonE
= Invisible
P.yES
= Modification can be done.
P. no
= Only visible.
Parameters of
menu
A.ALr..
=
ALr.o
menu access level code.
nonE
= Invisible
P.yES
= Modification can be done.
P. no
= Only visible.
Parameters of
A.CNf.
=
ConF.
access level code.
nonE
= Invisible
P.yES
= Modification can be done.
P. no
= Only visible.
Parameters of
menu
A.tun.
=
S.tun.
access level code.
no
= Invisible
yES
= Self tune can be done.
Parameters of
menu
SET
CSET
ASET
ASET
25
Pid.t.
After
PID is
calculated
Page 2/5
ConF. Page 2/5
d.adr.
1
baud
off
d.adr.
= Device address.
Adjusable between 1 and 247. Difference addresses
should be selected for every device.
Baud
= Modbus baud rate.
Selectable 1200, 2400, 4800 and 9600.
If
baud
=
off
, Modbus communication will be
disable.
U.sC.l.
-
999
U.sC.H.
4000
d.pnt.
0
U.sC.l.
= Lower scale value for mA inputs.
Adjustable between -999 and the (
U.sC.H.
- 100)
NOTE! If
Inp
is selected one of the mA input types, this
parameter is seen.
U.sC.H.
= Upper scale value for mA inputs.
Adjustable between (
U.sC.l.
+ 100) and 4000.
NOTE! If
Inp
is selected one of the mA input types,
this parameter is seen.
d.pnt.
= Decimal point for mA inputs.
Adjustable between 0 and 2.
NOTE! If
Inp
is selected one of the mA input types,
this parameter is seen.
Process value is
equal or lower than
60%of the set point ?
Yes
No
25
REdY.
Press
any key
70
TE.Hi.
When process value decreases
appropriate temperature
to self tune
Press any key
to deactivate
the self-tune procedure.
25
P.SE.t.
press and hold
While holding key,
run
message flashes. Then when key is pressed, self tune mode is entered if there is no probe failure. If process value is
appropriate to begin self tune,
rEdY.
message flashes. Then press any key to see
Pid.t.
message and self tune procedure begins.
Process value must be equal or lower than 60%of the setpoint to begin self tune procedure. If not,
tE.Hi.
message flashes and device waits to decrease
appropriate temperature to begin self tune. Then
rEdY.
message flashes and press any key to begin sellf tune procedure.
Before self tune procedure,
A.tun.
parameter must be selected
yES
from the
SECU
menu.If self tune is achieved
A.tun.
parameter becomes
no
automatically
and
S.tun
menu is canceled. Before self tune procedure, temperature setpoint value should be adjusted. When self tune procedure begins with no failure,
Pid.t.
message flashes and remains during the calculation of PID parameters. When PID parameters are calculated,
P.SE.t.
message flashes. Then the device
heats until setpoint value according to PID parameters and calculates the energy requirement for stable temperature and writes
P.SE.t.
parameter as %and run
mode enters.
If any key is pressed while
Pid.t.
message flashes, self tune prosedure is deactivated before calculation of PID parameters. If any key is pressed while
P.SE.t.
message flashes, then self tune prosedure is deactivated as PID parameters are calculated and
P.SE.t.
parameter is done
0.
t..oF.E.
no
t.oF.E.
= Control outputs on/off key,activation parameter.
If
t.oF.E
=
no
,To make the on/off outputs; key is not used.
If
T.Of.E
=
yES
, To make the on/off outputs; key is used.