ENDA ET1411 Скачать руководство пользователя страница 2

SET

SET

 ET1411

ENDA

OUT

°F

°C

   ET

1

411-E-06-R

2/2

The lower limit 
of the setpoint.

Control mode

While holding           key OUTPUT setpoint value appears and by using       and       keys 
the value can be adjusted.

C.typ

Programming Mode

Run Mode

Process 
Value

 30.0

29.9

30.0

o.lol

1000

        If both         keys are pressed and held for 3 seconds, 
                            programming mode is entered.

The offset value 
for the output

o.off

Output 
hysteresis

o.Hys

Decimal place

T

he upper limit 

of the setpoint.

o.uPl

Unit

22.0

               If both         keys are pressed,
                                    run mode is entered.

ou

Cn

Security parameter 
for configuration menu

A.

-

Cn

Security parameter 
for output setpoint value

A.ou.S.

A.

-

ou

Security parameter 
for output menu

S.Cod

Access code for security menu. 
This parameter should be  

321

 .

o.PPF

o.PPn

On time for the output 
in the case of 
probe failure.

Off time for the output 
in the case of 
probe failure.

Temperature unit

dres

Menu of Output control parameters

o.HYS

o.LoL
o.uPL

o.oFF

Output hysteresis

The lower limit of the setpoint.

T

he upper limit of the setpoint.

The offset value for the output

ou

-60.0                 

 -20.0                    

   0.1                       

o.LoL

      150.0            

  MIN

 UNIT

  MAX

  DEF.
  SET

o.PPn

On time for the output in the case of probe failure.

o.PPF

Off time for the output in the case of probe failure.

A. ou

-

A.ou.S.

A. Cn

-

Security parameter for 
menu of output control

= Menu is invisible.

NonE

P.yes

P.no

= Parameters of menu are changeable.

= Parameters of menu are only visible.

= Setpoint value is changeable.

= Setpoint value is only visible.

P.yes
P.no

Security parameter for 
menu of configuration

Security parameter for 
output setpoint value

Unit

dres

Temperature unit

Decimal place  (

no

      = 

no decimal point,        

22

 °C  

                           

yes 

= with

 decimal point,  

22.3

 °C )

C.tyP

Control mode    (

Heat

    = Heating cotrol

                             

Cool

     

°C           °F                      °C

=Cooling control)

o.uPL

-60

°C

°C

150

°C

°C

0

20.0

2

20.0

    0                       

255

Min.

  0

    0                       

255

Min.

  1

Heat

Cool

Heat

 no

yes

 no

Menu of Configuration

Cn

Menu of Parameter security

SE

PARAMETER TABLE

Used for selecting menu and increasing setpoint value of the parameters in the programming mode and for increasing the setpoint value in the run mode

.

 When held down for a 

few seconds, the change rate accelerates.

Used for selecting parameters and decreasing the setp

oint value

 in the programming mode and for decreasing the setpoint value in the run mode

.

 When held down for a few 

seconds, the change rate accelerates.

  OUT
  LED

FAHRENHEIT
  LED

Displayed process value in the run mode, parameter name or value in programming mode.

Used for adjusting the value of the setpoint in the run mode and for adjusting the selected parameter in the programming mode. While holding         key, setpoint value of the 
selected parameter  appears and by using         and         keys the value can be adjusted.

 Pfa

Means, thermostat probe is short circuit.

 PsC

Means, thermostat probe is broken.

Error Messages

Temperature value is higher than the scale.

Temperature value is lower than the scale.

Se

SET

SET

SET

SET

SET

SET

SET

SET