Doc. No: 01999901 

Revision: A 

1 of 10

 

Issue Date: 08/15/21

 

 

INSTALLATION 

 OPERATION 

 MAINTENANCE MANUAL 

 

 

 

 

SAF-T-TUB™ JUMP TANK 

 

MODEL: 01052539 

PRODUCT DESCRIPTION 

SAF-T-TUB™ Jump Tank system is designed to provide emergency treatment of personnel exposed to pyrophoric oxidizing 
agents or in situations when high heat irritants of thick density are involved. The heated re-circulating water bath with its 
ergonomic design allows for immediate extinguishing and preliminary decontamination in the 165 gallons of potable water, 
which can be treated with Encon Safety Products Hydrosep

Ò

 QT water preservative. 

 

SAF-T-TUB™ FEATURES 

 

¨

  165 gallon capacity 

¨

  79” x 30” x 38” full immersion depth 

¨

  Heated to maintain 85

°

F maximum 

¨

  Re-circulating to provide even temperature 

throughout 

¨

  Level indication and heater control 

¨

  Ergonomic design 

 

 

¨

  Double wall insulated annular space 

¨

  Fire retardant FRP/Gelcoat

Ò

 design 

¨

  Drain valve 

¨

  Isolated utility tank 

¨

  1.5 KH immersion heater 

¨

  Operation indicator lights: Power, Heater, Pump & 

Water Level 

¨

  Two thermostats 

Gelcoat

Ò

 is a registered trademark of Fibre de Verre Gar 

Fiberglass 

SPECIFICATIONS 

 

VOLUME 

165 Gallon potable water capacity 

 

WATER TEMPERATURE 

Maintains  70-85

°

F  through  use  of  a  1.5  KW  two  thermostats  and  level  switch 

control circuit 

 

ELECTRICAL REQUIREMENT 

13.1 amp, 120 volt circuit  

 

GFCI 30mA EPD type circuit protector is required (by others) 

 

ELECTRICAL CLASSIFICATION 

NEMA 4, and Class 1 Div. 2 Group D models are available 

WEIGHT 

175 lbs. tare 

1545 lbs. full 

DIMENSIONS 

Overall: 

78” (L) x 35” (D) x 40” (W) 

 

Inside Tank:  71 1/2” (L) x 28-3/4” (D) x 27” (W) 

CONSTRUCTION 

Double wall insulated fire retardant FRP, R-6 insulation factor 

CONTROLS 

Dual thermostat: Close 70

°

F; Open at 85

°

Water level control protection of the immersion heater and recirculating pump 

 

INDICATOR LIGHTS

 

Power On: GREEN ; Heater On: RED ; Pump On: ORANGE  

PUMP 

100 GPH Submersible

 

 

GENERAL INFORMATION 

1.  SAF-T-TUB™

 

should be installed in the facility near the point of potential contact, away from the irritant chemical potential 

spray area.  

2.  Placement of SAF-T-TUB™

 

should be in an area where the path of travel is free of obstructions that may inhibit the 

immediate use of the SAF-T-TUB™

 

and the area should be well lit. 

3.  SAF-T-TUB™

 

should be available for immediate use, and should be installed, inspected, and maintained in accordance 

with the manufacturer’s instructions. 

4.  Consideration should be given to the proper disposal of waste flushing fluid.

 

5.  This product should not be used as a substitute for proper emergency decontamination equipment. 
 

Содержание 3661

Страница 1: ...SAF T TUB JUMP TANK MODEL 01052539 S N 3661 INSTALLATION OPERATION AND MAINTENANCE MANUAL 01999901 Revision A 08 15 2021 ...

Страница 2: ...TURE Maintains 70 85 F through use of a 1 5 KW two thermostats and level switch control circuit ELECTRICAL REQUIREMENT 13 1 amp 120 volt circuit GFCI 30mA EPD type circuit protector is required by others ELECTRICAL CLASSIFICATION NEMA 4 and Class 1 Div 2 Group D models are available WEIGHT 175 lbs tare 1545 lbs full DIMENSIONS Overall 78 L x 35 D x 40 W Inside Tank 71 1 2 L x 28 3 4 D x 27 W CONST...

Страница 3: ...re the unit is being controlled properly and no visible leaks are present POWER ON and PUMP ON indicator lights should be illuminated NOTE If water temperature is below 70 F the HEATER ON indicator light should be illuminated See Junction Box Detail drawing attached OPERATION MAINTENANCE WARNING WARNING WARNING PROPER PERSONAL CARE SHOULD BE TAKEN TO AVOID BURNS AND ELECTRIC SHOCK DISCONNECT POWER...

Страница 4: ...Locate pump clamp and remove clamp using a flat head screwdriver d Remove pump from instrumentation compartment and disassemble for cleaning Refer to Figure 1 e Remove the screen intake 2 and volute plate 3 f Carefully remove the o ring 4 Caution should be taken to avoid damage to o ring g Lightly clean any corrosion or debris which may clog the impeller 5 h Use a brush and penetrating oil and lig...

Страница 5: ... water temperature is below 70 F 1 TAS shuts off heater when water temperature is over 85 F Remove and replace defective thermostat 2 1 CON must be energized Check using voltmeter at Terminals 3 5 Replace contactor if not energized 3 Check heater terminals Electrical terminals should be tight free of oxide build up 1 HTR must be energized Check using voltmeter at TB5 to 2W3 Replace heater if all t...

Страница 6: ...Doc No 01999901 Revision A 5 of 10 Issue Date 08 15 21 INSPECTION TEST REPORT ...

Страница 7: ...Doc No 01999901 Revision A 6 of 10 Issue Date 08 15 21 ...

Страница 8: ...Doc No 01999901 Revision A 7 of 10 Issue Date 08 15 21 ...

Страница 9: ...Doc No 01999901 Revision A 8 of 10 Issue Date 08 15 21 ...

Страница 10: ...f original ownership as proof of warranty coverage and Encon must receive any claim under this Limited Warranty within one year of purchase of the product NOTWITHSTANDING ANYTHING TO THE CONTRARY CONTAINED HEREIN ENCON SHALL NOT BE LIABLE FOR LOSS DAMAGE OR EXPENSE ARISING DIRECTLY OR INDIRECTLY AS A CONSEQUENCE OF USE OF THE EQUIPMENT WITH OTHER PRODUCTS OR FROM ANY OTHER CAUSE INCLUDING ANY CONS...

Страница 11: ...Doc No 01999901 Revision A 10 of 10 Issue Date 08 15 21 DRAWINGS ...

Отзывы: