Settings & Display
Extend Detect
DIP Switch
Extend Detect
mode extends the detection after the vehicle
leaves the loop for the extension time specified by DIP switch 7
and 8. When the vehicle is no longer detected and the operator
enters the extended detection time period, the red LED will flash.
8
7
No Extension
off
off
3 Second Extension
on
off
6 Second Extension
off
on
9 Second Extension
on
on
Automatic
Sensitivity Boost
DIP Switch 6
Automatic Sensitivity Boost
mode increases the sensitivity to
maximum when detection occurs. This allows for the continual
detection of high bed vehicles that might otherwise not be
detected. The sensitivity returns to normal after the vehicle exits
the loop.
ASB
On
on
ASB
Off
off
Filter
DIP Switch 5 Filter
mode inputs a momentary delay into the detection circuit to
verify that a vehicle is present in the loop for a minimum time
period before activation occurs.
Filter On
on
Filter Off
off
Fail Safe/
Fail Secure
DIP Switch 4
Fail Safe
mode activates the presence output in the event of a
loop failure.
Fail Secure
mode will not activate the presence
output in the event of a loop failure and the detector will not
change states on power loss or power up. In Fail Secure mode
relay 2 will trigger if a loop fault occurs.
Do not use Fail Secure
for reversing loop applications.
Fail Safe
on
Fail Secure
off
Presence
DIP Switch 3
4 Minute
presence mode causes the output to reset after 4
minutes.
Infinite
presence mode causes the output to remain in
detection mode as long as the vehicle remains near the loop.
Do not use 4 Minute presence mode for reversing loop
applications.
4 Minute
on
Infinite
off
Relay 2
Pulse Mode
DIP Switch 2
When in pulse mode (DIP switch 1 is off),
DIP switch 2 determines when the pulse occurs.
When DIP switch 2 is on
, Pulse on Un-Detect
,
relay 2 will pulse when the vehicle exits the loop.
When DIP switch 2 is off,
Pulse on Detect
, relay 2
will pulse when the vehicle enters the loop.
Pulse on Un-Detect
on
Pulse on Detect
off
Relay 2
Pulse/Presence
DIP Switch 1
DIP Switch 1 toggles between assigning the
relay 2 outputs to
Presence
or
Pulse
mode.
Presence
on
Pulse
off
Sensitivity Setting
The 10-position rotary switch allows for adjustment of the detection level.
The sensitivity threshold increases from position 0 (lowest setting) through
9 (highest setting). Typical applications require a setting of 3 or 4. The rotary adjustment
must be set to a specific/whole number. There are no half settings.