Troubleshooting

In the rare event of an issue with the device’s operation, refer to the points below:

Device not releasing upon a fire alarm condition?

 

Check that the device is added correctly to the system and that it is fault free at  

 

the FireCell radio hub.

 

Check that the door closes freely when closed manually.

 

Check that the plunger has a minimum of 10mm clearance between the ferrule  

 

and the floor / floor plate.

 

 

Check that the WDC’s output properties are set correctly within the control panel  

 programming.

Why does the fire door not close freely?

 

Check that the ferrule is not worn or damaged. Replace as necessary.

 

Check that the plunger has a minimum of 10mm clearance between the ferrule  

 

and the floor / floor plate.

Device not holding the door in an open position

 

Check that the plunger is depressed fully.

 

Check that the device is added correctly to the system and fault free at the   

 

FireCell radio hub.

 

Check that the device is positioned low enough for a good connection between  

 

the ferrule and the floor plate. The optimum plunger movement is 10 - 15 mm.

Device in tamper fault?

 

Check that the device is fixed correctly to the door.

 

Check that the surface is flat and that the tamper switch is engaging correctly,  

 

when the device is fixed to the door.

Battery fault / device not powered?

 

Check the polarity and the voltage of the batteries.

 

Check that the battery cover is fitted correctly.

 

Do NOT Press the log on button on a pre-programmed device, as this will cause  

 

communication with the control panel to be lost. Should this happen, delete the  

 

device from the system and add it back on.

Содержание FireCellWDC

Страница 1: ...2019 EMS Ltd All rights reserved MK241 Iss 2 20 11 2019 AJM Installation Guide...

Страница 2: ...only Assign device Position template against door Drill fixing positions Fix unit to door Position floor plate Mark floor plate fixing positions Drill floor plate fixing positions Fix floor plate to f...

Страница 3: ...installation Part no Product description FC 60 2000 FireCell Wireless Door Control Black FC 60 2010 FireCell Wireless Door Control White Installation must conform to applicable local installation code...

Страница 4: ...batteries When fitting replacing batteries observe correct polarity using only specified batteries Indication LED Note upon first power up the device will initiate a startup sequence denoted by a seri...

Страница 5: ...on Loop Module refer to the Fusion Loop Module Engineers Guide TSD062 for programming details Skip this step If the device has been supplied as part of a pre programmed system as this will cause commu...

Страница 6: ...to the system From Unassigned Dev Assign Device Assign All Dev 000 of 001 changing to Done 001 of 001 once complete To Exit BACK Position template against door If the device is to be fitted to a metal...

Страница 7: ...9 EMS Ltd All rights reserved Page 7 of 16 MK241 Iss 2 20 11 2019 AJM Use all four fixing positions Use supplied fixing screws Fix unit to door 2 5mm Drill fixing positions Drill all four fixing posit...

Страница 8: ...ved Page 8 of 16 MK241 Iss 2 20 11 2019 AJM Mark floor plate fixing positions Use small floor plate if bumpstop creates a trip hazard Mark all four fixing positions Position floor plate Door Bump stop...

Страница 9: ...Page 9 of 16 MK241 Iss 2 20 11 2019 AJM Fix floor plate to floor Use all four fixing holes Use supplied fixing screws Drill floor plate fixing positions Before drilling check locations of water pipes...

Страница 10: ...tem To add devices by ident post installation From Front Display Add New Device Select Desired RCC 01 Set Loop 1 Addr 003 Add By Ident Add Dev 01ABC Y Enter the Device s ident Enter the device type In...

Страница 11: ...2019 EMS Ltd All rights reserved Page 11 of 16 MK241 Iss 2 20 11 2019 AJM Test device...

Страница 12: ...of 10mm clearance between the ferrule and the floor floor plate Device not holding the door in an open position Check that the plunger is depressed fully Check that the device is added correctly to t...

Страница 13: ...acturer Replace remove and re insert batteries as appropriate During device startup sequence motor operation Beep sequence Low Low High repeated until the plunger releases High Low Low Low repeated un...

Страница 14: ...ult in poor performance Supply voltage 2 22 to 3 3 VDC Current consumption 60 A Operating frequency 868 MHz Output transmitter power Auto adjusting 0 14 dBm 0 25 mW Signalling protocol X2 Dimensions W...

Страница 15: ...Certification body CPR certificate DOP 0359 CPR 00648 EMS Ltd Technology House Herne Bay Kent CT6 8JZ United Kingdom 0359 EMS declares that the radio equipment type FireCellWDC is in compliance with D...

Страница 16: ...lishing EMS reserves the right to change any information regarding products as part of its continual development enhancing new technology and reliability EMS advises that any product literature issue...

Отзывы: