background image

TX

RESET

RX

BACK

HEALTHY

FAULT

SYS FAULT

LOOP 1

+

-

IN   OUT    IN    OUT

+

-

LOOP 2

+

-

IN   OUT    IN    OUT

+

-

RF1

RF2

TX

RX

TX

RESET

LOGON

RX

BACK

HEALTHY

FAULT

SYS FAULT

LOOP 1

+

-

IN   OUT    IN    OUT

+

-

LOOP 2

+

-

IN   OUT    IN    OUT

+

-

LOOP 3

+

-

IN   OUT    IN    OUT

+

-

LOOP 4

+

-

IN   OUT    IN    OUT

+

-

RF1

RF2

TX

RX

Operating

Temperature

   

-10°C to 55°C

Storage

Temperature

  

5°C to 30°C

Humidity  

Up to 95% non-condensing

Operating Voltage

 

17 to 28Vdc

Typical Operating

Current  

24mA@24Vdc loop powered (1st loop)

 

 

 

+7mA per each connected loop

IP Rating 

 

IP54

Operating Frequency

 868MHz

Output Transmitter

Power

  

 

0 - 14 dBm (0 - 25 mW)

Dimensions

 

 

270mm (W) 205mm (H) 75mm (D)

Weight

 

  0.95kg 

2012/19/EU (WEEE directive):

Products marked with this symbol cannot be 

disposed of as unsorted municipal waste in the 

European Union. For proper recycling, return this 

product to your local supplier upon purchase of 

equivalent new equipment, or dispose of it at 

designated collection points. For more information 

see www.recyclethis.info

European Union 

directives

EMS declares that the radio equipment type FireCell 

Radio Hub is in compliance with Directive 

2014/53/EU. The full text of the EU declaration of 

conformity is available at the following internet 

address: 

www.emsgroup.co.uk 

Approved to

EN54-18:2005. Fire detection and fire alarm 

systems. Part 18: Input/output devices.

EN54-25:2008. Incorporating corrigenda 

September 2010 and March 2012. Fire detection 

and fire alarm systems. Part 25: Components using 

radio links.

Certification

     

Certification body

  

CPR Certificate DOP

  0359-CPR-0028

9 Configuration

The Radio Hub’s programming and loop address are configured 

within the menu structure of the Radio Hub. 

8 Applying Power

Apply power to the Control Panel. The normal LED states for the 

Radio Hub are as below:

10 Close Radio Hub

Ensure that the Radio Hub PCB is correctly inserted and that 

the PCB retaining screws are refitted.

Refit the Radio Hub lid, ensuring the LEDs are not damaged by 

the light pipe when refitting.

POWER

FAULT

SYSTEM

FAULT

RADIO HUB

Healthy LED - Green LED will be on. 
Fault LED - Yellow LED will be off. 
Sys Fault LED -  Yellow LED will be off. 

7 Connection Wiring

Loop cables should only be 

passed via the access 

points available.

Flame retardant cable 

glands must be used.

DO NOT leave excess cable 

in the Radio Hub.

Repeat for 

Loops 2, 3 

and 4 if used.

Radio Hub Loop 1 connection

+ -

Control Panel

Loop 1

LOOP 1

+

-

     IN              OUT    

+

-

LOOP 2

+

-

IN   OUT    IN    OUT

+

-

+ -

OUT

IN

Refer to the programming manual (Doc Ref: MK98) for details of 

compatible FireCell devices and full programming information.

Free to download from 

www.emsgroup.co.uk 

0359

10

Manufacturer    

EMS Ltd. Technology House, Herne Bay, Kent, 

 

 

 

CT6 8JZ, United Kingdom

Year of 

manufacture

   

See devices serial number label 

Regulatory Information

Specification

©2018 EMS Ltd. All rights reserved                                                                      Page 2 of 2 

TSD052 Iss 17  05/09/2018   AJM

All manuals and user guides at all-guides.com