TX
RESET
RX
BACK
HEALTHY
FAULT
SYS FAULT
LOOP 1
+
-
IN OUT IN OUT
+
-
LOOP 2
+
-
IN OUT IN OUT
+
-
RF1
RF2
TX
RX
TX
RESET
LOGON
RX
BACK
HEALTHY
FAULT
SYS FAULT
LOOP 1
+
-
IN OUT IN OUT
+
-
LOOP 2
+
-
IN OUT IN OUT
+
-
LOOP 3
+
-
IN OUT IN OUT
+
-
LOOP 4
+
-
IN OUT IN OUT
+
-
RF1
RF2
TX
RX
Operating
Temperature
-10°C to 55°C
Storage
Temperature
5°C to 30°C
Humidity
Up to 95% non-condensing
Operating Voltage
17 to 28Vdc
Typical Operating
Current
24mA@24Vdc loop powered (1st loop)
+7mA per each connected loop
IP Rating
IP54
Operating Frequency
868MHz
Output Transmitter
Power
0 - 14 dBm (0 - 25 mW)
Dimensions
270mm (W) 205mm (H) 75mm (D)
Weight
0.95kg
2012/19/EU (WEEE directive):
Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the
European Union. For proper recycling, return this
product to your local supplier upon purchase of
equivalent new equipment, or dispose of it at
designated collection points. For more information
see www.recyclethis.info
European Union
directives
EMS declares that the radio equipment type FireCell
Radio Hub is in compliance with Directive
2014/53/EU. The full text of the EU declaration of
conformity is available at the following internet
address:
www.emsgroup.co.uk
Approved to
EN54-18:2005. Fire detection and fire alarm
systems. Part 18: Input/output devices.
EN54-25:2008. Incorporating corrigenda
September 2010 and March 2012. Fire detection
and fire alarm systems. Part 25: Components using
radio links.
Certification
Certification body
CPR Certificate DOP
0359-CPR-0028
9 Configuration
The Radio Hub’s programming and loop address are configured
within the menu structure of the Radio Hub.
8 Applying Power
Apply power to the Control Panel. The normal LED states for the
Radio Hub are as below:
10 Close Radio Hub
Ensure that the Radio Hub PCB is correctly inserted and that
the PCB retaining screws are refitted.
Refit the Radio Hub lid, ensuring the LEDs are not damaged by
the light pipe when refitting.
POWER
FAULT
SYSTEM
FAULT
RADIO HUB
Healthy LED - Green LED will be on.
Fault LED - Yellow LED will be off.
Sys Fault LED - Yellow LED will be off.
7 Connection Wiring
Loop cables should only be
passed via the access
points available.
Flame retardant cable
glands must be used.
DO NOT leave excess cable
in the Radio Hub.
Repeat for
Loops 2, 3
and 4 if used.
Radio Hub Loop 1 connection
+ -
Control Panel
Loop 1
LOOP 1
+
-
IN OUT
+
-
LOOP 2
+
-
IN OUT IN OUT
+
-
+ -
OUT
IN
Refer to the programming manual (Doc Ref: MK98) for details of
compatible FireCell devices and full programming information.
Free to download from
www.emsgroup.co.uk
0359
10
Manufacturer
EMS Ltd. Technology House, Herne Bay, Kent,
CT6 8JZ, United Kingdom
Year of
manufacture
See devices serial number label
Regulatory Information
Specification
©2018 EMS Ltd. All rights reserved Page 2 of 2
TSD052 Iss 17 05/09/2018 AJM
All manuals and user guides at all-guides.com