1

 

Pre Installation

4 Power Device 

3 Fix Mounting Plate

2

 

Components

device

unpowered

(pins unlinked)

device

powered

(both pins linked) 

!

Installation must conform to applicable local installation 

codes and should only be installed by a fully trained 

competent person. 

Ensure that the device is installed as per the site survey.

The use of a non-metallic spacer should be considered if 

mounting the device on to a metal surface.

Do NOT Press the Log On button on a pre-programmed 

device, as this will cause communication with the Control 

Panel to be lost. Should this happen, delete the device from 

the system and add it back on.

Detector

Wireless Module

Mounting Plate

2

3

Remove the mounting plate from the wireless module by turning 

it anticlockwise. 

4

Use both mounting holes to ensure a firm fixing.

Use suitable fasteners and fixings.

Once powered, reassemble the device.

Wireless Detector

Installation Guide

FCX-170-001      Wireless Detector Base Only 

 

[3]

FCX-175-001 

  Heat A1R Detector Only   

 

[1]

FCX-176-001 

  Heat CS Detector Only   

 

[1]

FCX-177-001 

  Optical Smoke Detector Only 

 

[2]

Example shown:

FCX-177-001

FCX-170-001

Part No           Product Description

See the Specification section for compliance information.

CPR

SIZE AA

SIZE AA

SIZE AA

SIZE AA

SIZE AA

SIZE AA

ATTENTION

OBSERVE PRECAUTIONS

FOR HANDLING

ELECTROSTATIC

SENSITIVE

2

4

3

1

Dust Cover

1

When fitting / replacing batteries; observe correct polarity, 

using only specified batteries. 

Connect the power jumper across the PIN header.

The detector can also be 

locked into the wireless 

module. To do so, prior to 

refitting the detector, remove 

the cut out (shaded) section 

as shown.

5 Optional Device Locking

To lock the wireless module 

into the mounting plate, insert 

a 1.5mm Allen key into the 

allen key slot and turn 

clockwise as shown.

To unlock the wireless module 

from the mounting plate, 

insert a 1.5mm Allen key and 

turn anticlockwise to release 

as shown.

6 Device Unlocking

To unlock the detector from 

the wireless module, insert a 

1.5mm Allen key and lever the 

Allen key towards the outside 

of the device whilst turning the 

detector anticlockwise to 

release as shown.

©2018 EMS Ltd. All rights reserved                                                                      Page 1 of 2 