background image

RADIO CLUSTER COMMUNICATOR

POWER

FAULT

RESET

LOGON

BACK

HEALTHY

FAULT

SYS FAULT

RF1

RF2

Figure 9

POWER  1

POWER  2

+      -

+      -

OK

OK

DO NOT

ADJUST VR1

L   N

BATTERY FUSE

3.15AF  F2

 CONN4

FAULT RELAY

 CONN3

 CONN1

+v

Ba

tte

ry

0v

+v

O

ut

pu

t 0v

PLK1

N

O

N

C

C

PLK2

PL2

Temp

PL1

D

is

pl

ay

off

Charge

0v

 CONN5

PRIMARY

FUSE F1
 1ATH

 250V

 HRC

0V

+V

0V

+V

O

utput

Ba

tt

er

y

CONN3

C

N/C

N/O

CONN4

Fault

RESET

LOGON

BACK

HEALTHY

FAULT

SYS FAULT

RF1

RF2

Figure 9

POWER  1

POWER  2

+      -

+      -

OK

OK

9 Configuration

The RCC’s programming and loop address are configured within 

the menu structure of the Radio Hub. 

TX

RESET

RX

HEALTHY

FAULT

SYS

FAULT

LOOP 1

+

-

IN   OUT    IN    OUT

+

-

LOOP 2

+

-

IN   OUT    IN    OUT

+

-

RF1

RF2

8 Applying Power

Apply power to the power supply. The normal LED states for the 

RCC are as below:

10 Close RCC

Ensure that the RCC PCB is correctly inserted and the PCB 

retaining screws are refitted.

Refit the RCC lid, ensuring LEDs are not damaged by the light 

pipe when refitting.

Healthy LED - Green LED will be on. 
Fault LED - Yellow LED will be off. 
Sys Fault LED -  Yellow LED will be off.
Power 1 LED - Green LED will be on.

 

Power 2 LED - Green LED will be on. 

7 Connection Wiring

Power cables should only be passed via the access points 

available.

Flame retardant cable glands should be used.

DO NOT leave excess cable in the RCC.

RADIO CLUSTER COMMUNICATOR

POWER

FAULT

Operating

Temperature

   

-10°C to 55°C 

Storage

Temperature

   

5°C to 30°C

Humidity  

Up to 95% non-condensing

IP Rating 

 

IP54

Operating Voltage 

17 to 28Vdc

Power Requirements 

17mA @ 24Vdc

Operating Frequency

 868MHz

Output Transmitter

Power

   

 

Auto adjusting 0 - 14 dBm (0 - 25 mW)

Dimensions

 

 

270mm (W) 205mm (H) 75mm (D)

Weight

 

  0.95kg 

Application

 

 

Indoor use only

2012/19/EU (WEEE directive):

Products marked with this symbol cannot be 

disposed of as unsorted municipal waste in the 

European Union. For proper recycling, return this 

product to your local supplier upon purchase of 

equivalent new equipment, or dispose of it at 

designated collection points. For more information 

see www.recyclethis.info

Certification

Certification body

 

CPR Certificate DOP

 0359-CPR-0046

Approved to   

EN54-18:2005. Fire detection and fire alarm  

 

 

 

 

systems. Part 18: Input/output devices.

 

 

 

EN54-25:2008. Incorporating corrigenda September  

 

 

 

2010 and March 2012. Fire detection and fire alarm  

 

 

 

systems. Part 25: Components using radio links.

European Union

directives

  

Refer to the  programming manual (Doc Ref: MK98) for full 

programming information.

0359

Free to download from 

www.emsgroup.co.uk 

12

Regulatory Information

Specification

Manufacturer    

EMS Ltd. Technology House, Herne Bay, Kent, 

 

 

 

CT6 8JZ, United Kingdom

Year of manufacture

  See devices serial number label 

EMS declares that the radio equipment type FireCell 

24Vdc RCC is in compliance with Directive 

2014/53/EU. The full text of the EU declaration of 

conformity is available at the following internet 

address: www.emsgroup.co.uk 

©2018 EMS Ltd. All rights reserved                                                                      Page 2 of 2                                                                         TSD054 Iss 8  05/09/2018   AJM