background image

Wireless Manual Call Point (Apollo Front)

Installation Guide

1 Pre installation

4 Power device 

When fitting / replacing batteries; observe correct polarity, 

using only specified batteries. 

Connect the power jumper across the PIN header.

3 Fix mounting plate

2 Components

Part no           Product description

!

Installation must conform to applicable local installation 

codes and should only be installed by a fully trained 

competent person. 

Ensure that the device is installed as per the site survey.

The use of a non-metallic spacer should be considered if 

mounting the device on to a metal surface.

Do NOT Press the Log On button on a pre-programmed device, 

as this will cause communication with the Control Panel to be 

lost. Should this happen, delete the device from the system and 

add it back on.

This device contains electronics that may be susceptible to 

damage from Electrostatic Discharge (ESD). Take 

appropriate precautions when handling electronic boards.

Remove the mounting plate from the wireless call point. See 

Step 5 for more information on unlocking the device.

5 Device locking

6 Configuration

When reassembling, observe 

the 

hinged connection 

located on the devices top 

edge first, prior to closing the 

unit. Finally lock the call point 

into the mounting plate by 

tightening the fixing screw.  

Use suitable fasteners and fixings.

FC-200-003 

   Wireless Manual Call Point (Apollo Front)

57 mm

67 mm

device

unpowered

(pins unlinked)

device

powered

(both pins linked) 

F

ixing screw 

Bottom view

of device

To open the call point, loosen 

the fixing screw, then slide 

the call point up, away from 

the   mounting plate.

4

5

3

Mounting plate

Wireless Call Point

4

5

Ensure mounting plate is fitted in the orientation shown.

1

Once powered, reassemble the device.

A minimum of 2 mounting holes 

must be used.

©2021 EMS Ltd. All rights reserved                                                                      Page 1 of 2 

MK289-99  Iss 3  23/11/2021   AJM

2

Fixing screw

3

Reset key

1

Transparent cover

2

REMOVE LABEL ON COMMISSIONING

REMOVAL

RESET

The device’s loop address is configured within the user interface’s 

menu structure. 

Refer to the programming manual for full programming details. 

Free to download from 

www.emsgroup.co.uk

FireCell = MK98

Fusion = TSD062

WZM = TSD143