EMS 827
GENSET CONTROLLER
Page 25
Message
Function description
Check the canopy temperature sensor and associated wiring.
Fuel-L Fault
The Fuel Level Sensor is not functioning as expected.
Check the Fuel Level Sensor and associated wiring.
Speed Fault
The Speed Sensing system is not working as expected.
Check the associated speed sensor wiring and external influences
such as poorly operating battery chargers and poorly filtered UPS
systems connect to the load.
Speed Detected
Speed signal is unexpectedly present.
Check the associated speed sensor wiring and external influences
such as poorly operating battery chargers and poorly filtered UPS
systems connected to the load. Check electrical safety earthing
systems. Check associated communications networks are isolated
and not part of an unexpected earth loop.
Oil Detected
Oil Pressure is unexpectedly present.
Check the Oil Pressure Sensors and associated wiring.
Check the Oil filter system is not blocked.
Check the engine is not running with a failed speed sensing system.
E-S Lock-out
The emergency stop input has been activated. Deactivate the
emergency stop input, then press the stop button to clear this
alarm.
Fire Alarm
The Fire Alarm input has been activated. The genset will be
shutdown as an emergency stop. Investigate the source of the
alarm then press the stop button to clear this alarm
A-S Lock-out
If the Stop button is pressed while running in auto mode, it is
considered an emergency stop and the unit will stop the engine and
enter the Autostart Lockout state. This prevents the engine from
starting again, while the Autostart input remains activated.
The Autostart Lockout state is self resetting upon deactivation of
the Autostart input.
If the engine was stopped for a real emergency, then the
emergency stop switch should also be activated to ensure the
engine will not start inadvertently.
If the unit is in the Autostart Lockout state, the engine can be
restarted by pressing the Start button. This is not considered a
manual start but rather a release from the Autostart Lockout
condition. The contactors will be controlled in the appropriate
way.