General installation information 

 
 
Absolute Maximum Ratings 

The Absolute Maximum Ratings are those limits for the device that, if exceeded, will likely damage the device. Exceeding the 
absolute maximum ratings voids any warranty and/or guarantee. 

 
Mounting 

Mounting of the product should be done in such a way that:

 

-

 

the absolute maximum ambient temperature rating of the product will never be exceeded. 

-

 

maximum cooling (direction of cooling ribs and direction of airflow) is achieved. 

-

 

Mounting no humid air can flow through the product or condensation occurs. 

-

 

dust or other materials or residue will not remain in or on the product. 

-

 

the maximum vibration is not exceeded. 

-

 

personal contact with persons is impossible. 

 

Wiring 

-

 

Diameter size of the wiring should be enough to carry the expected current. Wire insulation should be enough to withstand 
the expected operating voltages and temperatures. 

-

 

To improve EMC emission and immunity, care should be taken for the lay out of the wiring. This in respect to all wiring in the 
installation. 

-

 

Keep current carrying wires as short as possible. 

-

 

Keep wires carrying a total sum of zero Ampere close to each other, or in one single cable, E.g. U, V, W,  or  F1(+) and F2(-), 
or Phase and neutral, or S and T. 

-

 

Avoid current carrying conductors next to sensing or control wiring. Especially current controlled by SCR’s or PWM controlled 
transistors. 

-

 

If sensitive sensing signal cables need to be laid across distance along other cabling, shielded cable is preferred. Keep the 
shield  as  long  as  possible  and  the  wiring  outside  the  shield  as  short  as  possible.  Do  not  solder  or  shrink  the  shield  to  a 
regular wire. Connect the original shield to ground at one side with an as large as possible contact surface. 

 

Additional installation information 

When the product is supplied by means of a transformer, it should never be an auto-transformer. Auto-transformers react as 
voltage sweep up coil and may cause high voltage peaks. 

-

 

Standard  fit  capacitors  or  over-voltage  suppressers  across  F1(+)  and  F2(-),  or  exciter  field  terminals  inside  the  generator 
should be removed. 

-

 

When the product is supplied by means of a transformer, it should be able to carry at least the maximum expected current. 
Advisable is, to have a transformer which can carry twice the maximum expected current. Inductive loads make voltage sacks 
and peeks into the secondary voltage of a transformer, from which the device may malfunction. 

-

 

It is not recommended to apply switches in dc outputs. It is preferred to use switches in the ac supply inputs of devices. In 
case it is unavoidable to have switches in the dc output of a device, action must be taken to avoid over voltage damage to the 
device due to contact arcing. Use a voltage suppressor across the output. 

-

 

It is not recommended to apply switches or fuses in the sensing lines. Defects can cause high voltage situations due to over-
excitation. 

-

 

When using a step down transformer in medium or high voltage generators, the transformer should be three phase (if three 
phase sensing), and the transformer should be suitable for acting as a sensing transformer. If the transformer is unloaded, 
connect a resistor to avoid voltage waveform distortion. 

-

 

The phase relation from the generator to the AVR is important. Also when voltage transformers and/ or current transformers 
are installed.  

-

 

When  using  a  step  down  or  insulation  transformer  in  the  droop  circuit,  phase  relation  from  the  generator  to  the  AVR  is 
important. 

-

 

CT’s wiring, connected to the AVR should never be grounded. 

-

 

Always disconnect electronic products, circuits and people before checking the insulation resistance (Megger check). 

-

 

Due to differences in generators impedance’s, EMC behavior is not predictable. Therefore the commissioner / installer should 
be aware of proper and correct installation.  

-

 

Large,  highly  inductive,  exciter  stator  windings  can  cause  destructive  high  voltage  peaks.  Adding  a  resistor  from  10  to  20 
times the exciter stator field resistance reduces voltage spikes. If necessary filter can be fitted additionally. (e.g. snubber, RC-
network) 

-

 

Upon problems during commissioning, faulty behavior or defects in the generator, consult the fault finding manual at our web 
site 

-

 

Some advises may be overdone or seem extraordinary, but since the electrical rules are the same everywhere, these advises 
are given. 

 

Содержание EMRI2490

Страница 1: ...EMRI2490 Voltage regulator for generators Instruction Manual V1 1 Product version V1 1 0 0...

Страница 2: ...d Commissioning information Revision history The manual does not cover all technical details of the product Specifications may be modified by the manufacturer without notice For further information th...

Страница 3: ...duct is more rugged and compact design to improve mechanical properties The unit is completely encapsulated for harsh environments The moulding compound protects against vibrations and is heat conduct...

Страница 4: ...Unom 24Vac Link 20 22 0 1k U V W clockwise Compound Exciter field T6 2U1 2V1 2W1 R1 V1 G2 A dv Setting Voltage V Voltage A dv Setting Stability P Prop Gain I Int time Terminals internally linked 11 9...

Страница 5: ...Manual V1 1 Page 5 of 8 Wiring diagram Wiring diagram with EMRI2490...

Страница 6: ...ns to T6 The current transformer should also always bring so much power in return for the current which is going through that the total excitation power output of T6 is always a bit too much The avr c...

Страница 7: ...nside the generator should be removed When the product is supplied by means of a transformer it should be able to carry at least the maximum expected current Advisable is to have a transformer which c...

Страница 8: ...ritime Genetech Co Ltd Tel 66 38301262 Fax 1 832 221 5642 Website semtecmaritime com Email ron northstarusa co UNITED ARAB EMIRATES Sharjah KDU Technical Services Tel 971 6 5575480 Fax 971 6 5575490 W...

Отзывы: