
Manual V1.2
Page 9 of 20
Commissioning set up
Commissioning set up
Start
(AVR Active / Generator running ! )
Underspeed protection
Done
Threshold underspeed
Underspeed
Slowly
Until led on
Setpoint underspeed
Underspeed
Very slowly
Until led off
Led not red flickering!
Nominal speed
G
M
Note:
It is recommended to turn
the potentiometer a little
further clockwise,
to allow for short
frequency dips.
Indication setpoints
Содержание LX10.2
Страница 1: ...LX10 2 Voltage regulator for generators Instruction Manual V1 2 Product version V1 1 0 0...
Страница 4: ...Manual V1 2 Page 4 of 20 Absolute maximum rating...
Страница 5: ...Manual V1 2 Page 5 of 20 Protections...
Страница 12: ...Manual V1 2 Page 12 of 20 Wiring diagram I AVR with PMG...
Страница 13: ...Manual V1 2 Page 13 of 20 Wiring diagram II AVR with auxilary windings self excited...
Страница 14: ...Manual V1 2 Page 14 of 20 Wiring diagram III AVR with transformer self excited...
Страница 15: ...Manual V1 2 Page 15 of 20 Wiring diagram IV AVR with generator phase supply self excited...
Страница 16: ...Manual V1 2 Page 16 of 20 Tips and Suggestions I...
Страница 17: ...Manual V1 2 Page 17 of 20 Tips and Suggestions II Field flash with isolated battery AVR...
Страница 18: ...Manual V1 2 Page 18 of 20 Tips and Suggestions III Field flash with isolated battery Exciter field...