Empire Comfort Systems VFNI-24N-1 Скачать руководство пользователя страница 10

28091-8-0814

Page 10

This is an unvented gas-fired heater. It uses air (oxygen) from the 

room in which it is installed. Provisions for adequate combustion 

and ventilation air must be provided.
Keep room area clear and free from combustible materials, gasoline 

and other flammable vapors and liquids.

Unvented gas heaters are a supplemental zone heater. They are not 

intended to be a primary heating appliance. Water vapor produced 

by an unvented heater can create moisture problems in a home 

when operated for extended periods of time.
During manufacturing, fabricating and shipping, various components 

of this appliance are treated with certain oils, films or bonding agents. 

These chemicals are not harmful but may produce annoying smoke 

and smells as they are burned off during the initial operation of the 

appliance; possibly causing headaches or eye or lung irritation. This 

is a normal and temporary occurrence.
The initial break-in operation should last 2-3 hours with the burner 

at the highest setting. Provide maximum ventilation by opening 

windows or doors to allow odors to dissipate. Any odors remaining 

after this initial break-in period will be slight and will disappear with 

continued use.
This appliance must not be used with glass doors in the closed 

position. This can lead to pilot outages and severe sooting outside 

the fireplace.

Do not use this room heater if any part has been under water. 

Immediately call a qualified service technician to inspect the room 

heater and replace any part of the control system and any gas 

control which has been under water.

 

WARNING

This appliance is equipped for (natural or propane) 

gas. Field conversion is not permitted.

Before you get started

Carefully inspect the contents for shipping damage. If any parts are 

missing or damaged, immediately inform the dealer from whom you 

purchased the appliance. Do not attempt to install any part of the 

appliance unless you have all parts in good condition.

Make sure you have received all parts:

Check your packing list to verify that all listed parts have been 

received. You should have the following:

•  Gas log grate/burner assembly.

•  Two (2) masonry anchoring screws and two (2) 10 x 1/2" black 

sheet metal anchoring screws.

•  Plastic bag containing glowing embers (rock wool) for burner 

coverage.

•  Plastic bag containing lava rock.
•  Switch log assembly - VFNR models
•  Remote kit - VFNI, VFXI, VFXV models
Millivolt controlled heater designed to be operated with optional 

devices for ON/OFF functions.

•  Wall switch or thermostat with wire.

•  Hand held remote control with ON/OFF switch or thermostat.

Handle the gas log burner assembly by the grate and legs only. 

Do not pick the unit up by the burner.

Gloves are recommended when handling logs to prevent skin 

irritation. Logs are fragile - Handle with care.
Qualified Installing Agency

Installation and replacement of gas piping, gas utilization equip-

ment or accessories and repair and servicing of equipment shall be 

performed only by a qualified agency. The term "qualified agency" 

means any individual, firm, corporation, or company that either in 

person or through a representative is engaged in and is respon-

sible for (a) the installation, testing, or replacement of gas piping 

or (b) the connection, installation, testing, repair, or servicing of  

equipment; that is experienced in such work; that is familiar with all  

precautions required, and that has complied with all the  

requirements of the authority having jurisdiction.

State of Massachusetts: 

The installation must be made 

by  a  licensed  plumber  or  gas  fitter  in  the  Commonwealth  of 

Massachusetts.

Sellers of unvented propane or natural gas-fired supplemental 

room heaters shall provide to each purchaser a copy of 527 

CMR-30 upon sale of the unit.

The installation must conform with local codes or, in the absence 

of local codes, with the National Fuel Gas Code, ANSI Z223.1.*

*Available from the American National Standards Institute, Inc. 11 

West 42nd St., New York, N.Y. 10018.

High Altitudes: 

For altitudes/elevation above 2,000 feet ratings 

should be reduced at the rate of 4 percent for each 1,000 feet above 

sea level. Contact the manufacturer.

Water vapor is a by-product of gas combustion. An unvented room 

heater produces approximately one (1) ounce (30ml) of water for 

every 1,000 BTU's (.3KW's) of gas input per hour. 
Unvented room heaters must be used as supplemental heat  

(a room) rather than a primary heat source (an entire house). In most 

supplemental heat applications, the water vapor does not create a 

problem. In most applications, the water vapor enhances the low 

humidity atmosphere experienced during cold weather. 

The following steps will help insure that water vapor does not 

become a problem.  
1.  Be sure the heater is sized properly for the application, including 

ample combustion air and circulation air.

2.  If high humidity is experienced, a dehumidifier may be used to 

help lower the water vapor content of the air.

3.  Do not use an unvented room heater as the primary heat source 

(an entire house).

GENERAL INFORMATION

WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS

Содержание VFNI-24N-1

Страница 1: ...for use with the type of gas indicatedontheratingplate Thisapplianceisnot convertible for use with other gases Installer Leave this manual with the appliance Consumer Retain this manual for future ref...

Страница 2: ...14 Before Fully Installing the Appliance 14 Gas Supply 15 Placement of Glowing Embers and Lava Rock 16 Operation Instructions Flame Appearance 16 VFNR 24 30 Lighting Instructions 17 VFXV 24 30 Lightin...

Страница 3: ...e pilot If the pilot IS lit 1 To ignite the burner press the high flame button there will be a beep for approximately 5 seconds until there is a soft click then release the button To ADJUST the Flame...

Страница 4: ...28091 8 0814 Page 4 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 5: ...ghts perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption o...

Страница 6: ...to avoid potential problems with sooting Sooting resulting from improper installation or operation can settle on surfaces outside the fireplace See instructions for proper installation WARNING Do not...

Страница 7: ...er than those supplied for use with the log set 6 Also refer to IMPORTANT SAFETY INFORMATION in the fireplace Owner s Manual WARNING DO NOT OPERATE THIS GAS LOG SET WITH GLASS DOORS CLOSED Clothing or...

Страница 8: ...appliance 3 Installer should show owner how to start and operate unvented room heater vented decorative appliance Always consult your local Building Department regarding regulations codes or ordinanc...

Страница 9: ...4 Propane Variable 38 000 28 000 VFNR 24 Natural Millivolt 38 000 27 000 VFNR 24 Propane Millivolt 38 000 28 000 VFNI 24 Natural Intermittent 38 000 27 000 VFNI 24 Propane Intermittent 38 000 28 000 V...

Страница 10: ...be operated with optional devices for ON OFF functions Wall switch or thermostat with wire Hand held remote control with ON OFF switch or thermostat Handle the gas log burner assembly by the grate and...

Страница 11: ...ned space must have 2 openings into the space for combustion air One opening must be within 12 inches of the ceiling and the other must be within 12 inches of the floor The required sizing of these op...

Страница 12: ...ded to at least 8 with the installation of the optional fireplace hood If you can not extend non combustible material at least 8 you must operate heater with flue damper open Mantel Clearances with Ho...

Страница 13: ...SOLID FUEL BURNING FIREPLACES Do not attach combustible material to the mantel of your fireplace This is a fire hazard Figure 7 No greeting card stockings or ornamentation of any type should be placed...

Страница 14: ...not seal the chimney flue damper Before installing in a solid fuel burning fireplace the chimney flue and firebox must be cleaned of soot creosote ashes and loose paint by a qualified chimney cleaner...

Страница 15: ...the bottom in which condensation and foreign particles may collect Figure 12 The use of the following gas connectors is recommended ANS Z21 24Appliance Connectors of Corrugated MetalTubing and Fittin...

Страница 16: ...iance are treated with certain oils films or bonding agents These chemicals are not harmful but may produce annoying smoke and smells as they are burned off during the initial operation of the applian...

Страница 17: ...r Wait 30 seconds before readjusting the heater when the control knob has been turned down to a lower setting FOR YOUR SAFETY READ BEFORE LIGHTING A This appliance has a pilot which must be lighted by...

Страница 18: ...ear of burner 6 Turn gas knob counterclockwise to IGN 7 Depress and turn gas control knob counterclockwise to PILOT A spark is produced when gas control knob is turned between IGN and PILOT Repeatedly...

Страница 19: ...out any gas then smell for gas including near the floor If you smell gas STOP Follow A in the safety information above If you don t smell gas go to the next step LIGHTING PROCEDURE HANDSET METHOD 1 T...

Страница 20: ...re 17 If pilot flame pattern is incorrect as shown in Figure 17 See Troubleshooting page 30 Cleaning and Maintenance Pilot Oxygen Depletion Sensor Pilot Figure 18 When the pilot has a large yellow tip...

Страница 21: ...ems discussed below Inspect and clean burner air intake hole Remove lint or particles with vacuum or brush Failure to keep air intake hole clean will result in sooting and poor combustion Inspect and...

Страница 22: ...ars 81 F to 90 F 27 C to 37 C SLEEP MODE After 8 hours off no signal between the handset and receiver valve runs to pilot and Sleep Mode Icon is displayed INITIAL SETUP Radio Frequency Remote A code i...

Страница 23: ...E TIMER PROGRAMMING MODE NOTE Use up button only to adjust menu items Numbers scroll up to the highest setting and then cycle back to the beginning number Tem perature setting cycle back to OFF or pil...

Страница 24: ...n remote control 750 Millivolt System When you ignite the pilot the thermocouple produces millivolts electrical current which energizes the magnet in the gas valve After 30 seconds to 1 minute time pe...

Страница 25: ...ence received including interference that may cause undesired operation Changes or modifications not expressly approved by the party responsible for compli ance could void the user s authority to oper...

Страница 26: ...NG C 24 HOUR OR F 12 HOUR CLOCK Display Timer Thermostat RF Remote Handsets Press OFF and small flame until display changes from Fahrenheit 12 hour clock to Celsius 24 hour clock and vice versa AUTOMA...

Страница 27: ...clicks until the end stops are reached This allows for manual flame height adjustment as well as adjustment to pilot standby po sition 1 STOP Read the safety information included before proceed ing 2...

Страница 28: ...ton on remote Follow appliance instructions for gaining accessibility to the gas control Place ON OFF switch in O off position Turn main valve knob to the OFF full clockwise position Replace appliance...

Страница 29: ...UPLE RF ANTENNA THERMO CURRENT CABLE 1 ON OFF SWITCH 8 WIRE CABLE INTERRUPTER BLOCK COMBINATION CONTROL MANUAL KNOB PIEZO IGNITER MAIN VALVE KNOB CONNECTION FOR MANUAL IGNITION THERMO CURRENT CABLE 2...

Страница 30: ...g is not correct Replace gas regulator 7 ODS pilot lights but flame goes out when control knob is released a Control knob not fully pressed in Press in control knob fully b Control knob not pressed in...

Страница 31: ...LOT LP 11 R5171 PILOT NAT 16 27170 VALVE BRACKET 17 R10597 VALVE MAXTROL NAT 17 R10598 VALVE MAXTROL LP 18 27190 EMBER BED ASSEMBLY 24 18 27194 EMBER BED ASSEMBLY 30 19 P308 EMBER BED ORIFICE NAT 19 P...

Страница 32: ...28091 8 0814 Page 32 PARTS VIEW 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 23 22 21...

Страница 33: ...Parts Heater Hearth and Grills Victor Division of F W Webb Company 200 Locust Street Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites w...

Страница 34: ...in accordance with the instructions furnished with the ap pliance A bill of sale cancelled check or payment record should be kept to verify purchase date and establish warranty period Ready access to...

Страница 35: ...28091 8 0814 Page 35 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Страница 36: ...t Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question please contact...

Отзывы: