30794-4-0513
Page 11
VENTING STOVE
Figure 6
SPECIAL VENTING NOTES:
DVP20CC NAT
-can be vented horizontally with kit DVK45NAT
maximum 18".
DVP20CC LP
- can be vented horizontally with kit DVK45LP
maximum 18".
DVP20CC (LP,NAT)
- can use a 14" short snorkel or 36" tall snorkel.
DVP30CC NAT
-
CAN NOT
be vented horizontally, straight out the
back. An initial 1' vertical rise is required before turning horizontal or
use of the Simpson Duravent 36" tall or 14" short snorkel is required.
DVP30CC LP
-
CAN NOT
be vented horizontally, straight out the
back. An initial 3' vertical rise is required before turning horizontal
or use of the Simpson Duravent 36" tall snorkel is required.
CAUTION
Total vertical run MUST BE completed before starting horizontal
run.
Horizontal chimney run must slope upward (away from
stove) 1/4" per foot and vent termination must be level.
Sidewall Venting
The maximum vertical and horizontal distances are 25 feet and 12
feet, respectively. Vertical dimensions are based on top of stove to
centerline of pipe. Horizontal dimensions are based on centerline
of pipe to termination.
Under no circumstances should combustible materials (including
siding) be closer than 3" from the top of the 6 5/8" pipe or closer
than 1" on the sides and bottom.
Cutting the Hole
After the appliance has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This hole
needs to be 9" high x 10" wide for 4 x 6 pipe and 10-1/2 x 10-1/2 for
5 x 8 pipe with its center line determined by the amount of vertical
arise and horizontal run of the termination. When locating the hole
it must be noted that the bottom of the cap must be 12" above the
ground level, and top of the cap must be no less than 18" below a
combustible projection, and no closer than 9" to any wall running
parallel to vent termination.
Co-Linear to Co-Axial Connection
A Co-Axial to Co-Linear appliance connector is approved for
installation in vertical venting applications. One can be purchased
through Empire Comfort Systems or Simpson Dealer (part number
46DVA-GCL).
CO-AXIAL to
CO-LINEAR
CONNECTOR
(SD46DVA-GCL)
FLEX PIPE
EXHAUST
INTAKE
STRAIGHT
CO-AXIAL
(DETERMINE LENGTH
NEEDED AND
PURCHASE SEPARATELY)
CHIMNEY LINER
TERMINATION KIT
VENT CAP
ROUND
to
CONNECTOR
CO-LINEAR
CO-AXIAL
VERTICAL
VENT KIT
(DVKI)
45º ELBOW
(SD46DVA-E45B)
Figure 7