VENTING AND INSTALLATION

Vent System Approvals

Figure 8 

shows the vent termination caps and systems approved 

for use with these models. Approved vent system terminations are 

labeled for identification. 3-inch diameter listed flexible aluminum 

or stainless steel gas vent is used for both the incoming combustion 

air and exhaust vent pipes. NO OTHER VENTING SYSTEMS OR 

COMPONENTS MAY BE USED. Detailed installation instructions 

are included with each vent termination kit and should be used in 

conjunction with this manual.

Horizontal Venting

The vent system on this model 

CANNOT 

be terminated 

horizontally.

Vertical Venting

The inlet and exhaust vent pipes 

MUST 

be connected to the proper 

collars on the unit 

AND 

to the termination cap or the unit will not 

operate. The intake vent collar is identified by a stamped “I” on the 

top collar sliding vent plate assembly.

 

WARNING

MAJOR U.S. BUILDING CODES SPECIFY MINIMUM 

CHIMNEY AND/OR VENT HEIGHT ABOVE THE ROOF TOP. 

THESE MINIMUM HEIGHTS ARE NECESSARY IN THE 

INTEREST OF SAFETY. SEE FIGURES 8 THROUGH 10 FOR 

MINIMUM HEIGHTS, PROVIDED THE TERMINATION CAP IS 

AT LEAST 2-FEET FROM A VERTICAL WALL AND 2-FEET 

BELOW A HORIZONTAL OVERHANG.

Note: 

This also pertains to vertical vent systems installed on the 

outside of the building.

 

WARNING

THE EXHAUST PIPE MUST ONLY BE CONNECTED TO THE 

EXHAUST STARTING COLLAR OF THE UNIT AND TO THE 

EXHAUST COLLAR OF THE TERMINATION CAP.
THE INLET AIR PIPE MUST ONLY BE CONNECTED TO THE 

INLET AIR STARTING COLLAR OF THE UNIT AND TO THE 

INLET AIR COLLAR OF THE TERMINATION CAP. BOTH THE 

INLET VENT AND THE FLUE VENT MUST BE CONNECTED 

FROM THE INSERT TO THE VENT TERMINATION CAP.

NOTICE

The minimum vertical vent rise is 10 feet and the 

maximum vertical vent rise is 35 feet. These dimensions are 

measured from the starting collars of the unit to the end of the last 

section of vent pipe. 

See Figure 8.

NOTICE

The damper of the masonry chimney may need to be 

removed to allow installation of the flexible-vent pipe.

When installing into a zero clearance, factory built wood-burning 

fireplace, the use of the DVKI Round Vertical Termination Kit should 

allow you to mount the vent adaptor and cap to the exposed  round 

chimney pipe easily.

Connecting the Vent Pipe

 

CAUTION

Sharp edges. Always use gloves when installing.

Install the 3-inch flexible vent pipes down through the chimney.

Attach the pipe-to-cap adaptor to the termination cap and the 

top of the flexible vent pipe, then install the cap to the top of the 

chimney. 
Remove the vent slide plate assembly from the top of the insert. 

See Figure 7. 

Trim off excess venting then attach and secure 

the bottom ends of the flex pipes to the starting collars with the 

adjustable band clamps provided. Slide the gas insert into place, 

and position any excess flex vent pipe back up into the chimney. 

Begin installation of the insert into the fireplace opening. Align the 

vent slide plate assembly with the guides located on top of the 

insert. Work the insert inch by inch into the fireplace cavity as you 

pull forward on the vent slide plate assembly. Do not use excessive 

force on the vent slide plate. Once the vent slide plate is close to 

seating, install the vent bolt through the center hole of the insert 

top flange, and into the vent slide plate nut. Using a wrench or 

socket, tighten the bolt until the vent slide plate is seated forward 

completely. 

Positioning, Leveling, and Securing Insert

1.  Place the insert into position.

NOTICE:

 The front flanges of the insert (without surround panels) 

should be set at approximately 1”(inch) in front of the face of the 

fireplace.

2.  Level the insert from side to side and front to back.

3.  If necessary, use the leveling bolts included in the instruction 

pack. Screw the legs into the nuts installed in the bottom of 

the insert. Turn legs in until insert is level.

 

CAUTION

TO AVOID DOWNDRAFTS AND/OR COLD AIR PROBLEMS, 

IT IS RECOMMENDED TO SEAL OFF THE AREA BETWEEN 

THE TERMINATION CAP AND THE TOP OF THE SOLID-

FUEL CHIMNEY OPENING INTO WHICH THE VENT CAP 

HAS BEEN INSTALLED.

Figure 7

Содержание DVL25IN33N-1

Страница 1: ...NG If the information in these instruc tions are not followed exactly a fire or explo sion may result causing property damage personal injury or loss of life WARNING HOT GLASS DO NOT TOUCH NEVER WILL...

Страница 2: ...y Information 16 Glass Placement 17 Operating Instructions 18 Standing Pilot Lighting Instructions 19 Standing Pilot Wiring 20 Standing Pilot Troubleshooting 21 IPI Electronic System Operating Instruc...

Страница 3: ...ass front or any part removed for servicing the appliance must be replaced prior to operating the appliance Work should be done by a qualified service person Keep burner and control compartment clean...

Страница 4: ...erform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wall...

Страница 5: ...West 42nd St New York N Y 10036 NOTICE Prior to operating this unit be sure to clean the interior porcelain coated liner panels and glass door with a soft clean cloth Due to normal manufacturing proc...

Страница 6: ...s and clamps Recommended when installing to a square or rectangular clay flue DVK35 Vent Extension Kit 35 flex vent extension section with 2 connectors and 4 clamps NOTICE When installing vent caps sp...

Страница 7: ...EPLACE INSERT DIMENSIONS all dimensions in inches MODEL A B C D E F G H I J K L M N O DVL25IN 28 16 1 2 15 10 1 2 25 1 4 12 3 4 17 18 5 16 27 6 7 8 9 1 4 20 22 1 4 40 22 1 2 DVL33IN 31 19 1 2 16 1 2 1...

Страница 8: ...ation of any type should be placed on or attached to the fireplace The flow of heat can ignite combustibles Figure 4 8 MINIMUM CLEARANCE TO PERPENDICULAR COMBUSTIBLE SIDE WALL FROM EDGE OF DOOR FRAME...

Страница 9: ...ne of the procedures results in pressures in excess of 1 2 psig 14 w c 3 5 kPa on the fireplace gas valve it will result in a hazardous condition Checking Manifold Pressures Both Propane and Natural g...

Страница 10: ...urround panel kits have been tested and approved to cover existing air circulation vents or grills NOTICE Cutting of sheet metal parts of a fireplace in order to install the fireplace insert is prohib...

Страница 11: ...y chimney may need to be removed to allow installation of the flexible vent pipe When installing into a zero clearance factory built wood burning fireplace the use of the DVKI Round Vertical Terminati...

Страница 12: ...CESS COVER PLATE BLOWER POWER CORD OPTIONAL ON OFF SWITCH LOCATION VENT CLAMPS RECTANGULAR TERMINATION CAP DVVK3FV KIT ROUND TERMINATION CAP DVKI KIT ROUND CO LINEAR TO CO AXIAL ADAPTOR 10 MINIMUM 35...

Страница 13: ...stem exposed to cold weather 4 Inspect joints to verify that no pipe sections or fittings have been disturbed and consequently loosened Also check mechanical supports such as wall straps or plumbers t...

Страница 14: ...d white wires as shown in Figure 13b Note This bypasses the On Off switch located on the unit s left hand side flange 3 Run the low voltage alternate switch wires over to the right or left surround pa...

Страница 15: ...THE FIREPLACE INSERT NEVER OB STRUCT OR MODIFY THE AIR INLET OUTLET LOUVERS ON THE FIREPLACE INSERT IN ANY MANNER SURROUND ASSEMBLY ENGAGE SIDE PANEL MAGNETS TO SIDE FLANGES ON INSERT BACK SIDE NOTE...

Страница 16: ...oval of the blower system must be performed by a qualified service person If the blower assembly must be replaced the following steps are recommended for removal 1 Turn off gas and disconnect the elec...

Страница 17: ...Glass should only be performed after the DVL Fireplace Insert has been fully installed secured and tested for leaks If operating the burner with a Remote Control make sure all batteries are installed...

Страница 18: ...ilot The pilot remains ON even when the main burner is OFF Whenyouignitethepilot thethermopileproducesmillivolts electrical current which energizes the magnet in the gas valve After 30 seconds to 1 mi...

Страница 19: ...applicable 13 Set REMOTE OFF ON switch to desired setting FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property...

Страница 20: ...PERATION AFTER SERVICING For Standing Pilot Ignition Wiring Appliance Requirements WARNING DO NOT CONNECT 110 120 VAC TO THE GAS CONTROL VALVE OR THE APPLIANCE WILL MALFUNCTION AND THE VALVE WILL BE D...

Страница 21: ...t bracket Check the thermopile with a millivolt meter Take the reading at TH TP TP terminals of the gas valve The metershouldread350millivoltsminimum whileholdingthe valve knob depressed in the PILOT...

Страница 22: ...and LIGHTING INSTRUCTIONS for In termittent Pilot controls found in this manual and on labels found in the control compartment located in the lower cavity of the appliance 2 During the operating seaso...

Страница 23: ...t is used CAUTION Do not operate the appliance with panel s removed cracked or broken Replacement of the panel s should be done by a licensed or qualified service person WARNING Improper installation...

Страница 24: ...structions for detailed operation information FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage person...

Страница 25: ...ions on page 24 and Wiring Diagram on page 23 Troubleshooting Before proceeding with the procedures in the following trouble shooting table verify that the power supply AC DC adapter is present and th...

Страница 26: ...ire harness 4 Replace the DFC board 1 Verify the electrical connections integrity and make sure they are in accordance with the relevant system wiring diagram If necessary replace the wire harness 2 I...

Страница 27: ...and verify voltage at ignition between the EV1 terminal and the ground connection on the valve body 5 1 If the voltage is greater than 0 then Replace Valve 5 2 Or Replace DFC 6 Check the pressure at...

Страница 28: ...g Glass Door Frequency After the first 3 to 4 hours of use As necessary after initial cleaning By Home owner Task Remove and clean glass after the first 3 to 4 hours of use After the initial cleaning...

Страница 29: ...L25IN 43 DVL33IN 22 1 4 DVL25IN 25 1 4 DVL33IN 6 2 1 4 6 28 DVL25IN 31 DVL33IN 14 DVL25IN 17 DVL33IN Black Used to raise insert and surround panels when installed in a fireplace without a flush hearth...

Страница 30: ...3 N P 1 22950 22950 22950 22950 FLUE CONNECTOR GUIDE 2 23309 23211 23309 23211 SLIDE PLATE ASSEMBLY 3 R9188 R9188 R9188 R9188 GASKET TOP 4 16223 27718 16223 27718 SPRING RETAINER ASSEMBLY 5 27666 2769...

Страница 31: ...5 28063 28063 28683 28683 VALVE BRACKET 26a R7577 R7577 R11125 R11125 VALVE SIT NAT 26b R7578 R7578 R11126 R11126 VALVE SIT LP 27 R6207 R6207 R6207 R6207 ELBOW 5 16 X 3 8 NPT 90 28 27147 27672 28791 2...

Страница 32: ...reet Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites www fwwebb com www victormfg com Parts Heater Hearth and Grills MASTER PARTS DISTR...

Страница 33: ...29209 0 0911 Page 33 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Страница 34: ...29209 0 0911 Page 34 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Страница 35: ...29209 0 0911 Page 35 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Страница 36: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Отзывы: