background image

This page intentionally left blank!

 

Содержание VS30

Страница 1: ...Emotron VS30 AC drive 3 7 5 kW Mounting and switch on instruction ...

Страница 2: ...This page intentionally left blank ...

Страница 3: ...ons 10 4 3 1 3 Terminal data 10 4 3 2 Connection to the IT system 12 4 3 3 CANopen connection 13 4 3 3 1 Connection plan 13 4 3 3 2 Terminal data 13 4 3 3 3 Basic network settings 13 4 3 4 Modbus connection 14 4 3 4 1 Connection plan 14 4 3 4 2 Terminal data 14 4 3 4 3 Basic network settings 14 4 3 5 Connection of the safety module 15 4 3 5 1 Important notes 15 4 3 5 2 Connection plan 16 4 3 5 3 T...

Страница 4: ...This page intentionally left blank ...

Страница 5: ...20 C Series 3 phase 400V Rated current 7 3A IP20 CANopen STD I O VS 30 40 016 20 M Series 3 phase 400V Rated current 16A IP20 MODBUS STD I O Information and tools with regard to the Emotron products can be found on the Internet http www emotron com services support file archive Read this documentation thoroughly before carrying out the installation and commissioning Please observe the safety instr...

Страница 6: ...t not exceed 110 VDC Observe all specifications of the corresponding documentation supplied This is the precondition forsafe and trouble free operation and for obtaining the product features specified The procedural notes and circuit details described in this document are only proposals It is up to the user to check whether they can be adapted to the particular applications Emotron does not take a...

Страница 7: ...e specified on High leakage current Carry out fixed installation and PE connection in compliance with EN 61800 5 1 or EN 60204 1 Hot surface Use personal protective equipment or wait until devices have cooleddown Motor If there is a short circuit of two power transistors a residual movement of up to 180 number of pole pairs can occur at the motor For 4 pole motor residual movement max 180 2 90 Thi...

Страница 8: ...x Option Network status LEDs Interface X16 Diagnostic module Control terminals X3 Standard I O or Application I O IT screw PTC input X109 Motor connection X105 Safety module X1 Slot Shield connection Control connections Memory moodule X20 Inverter status LEDs DIP switch Baud rate and bus adress CANopen Modbus ...

Страница 9: ...t notes Dangerous electricalvoltage Possible consequence death or severeinjuries All works on the inverter must only be carried out in the deenergised state After switching off the mains voltage wait for at least 3 minutes before you start working DANGER ...

Страница 10: ...7 Mounting Mechanical installation 4 4 2 Mechanical installation Dimensions 3 kW 5 5 kW All Dimensions in mm ...

Страница 11: ...8 4 Mounting Mechanical installation Dimensions 7 5 kW All Dimensions in mm ...

Страница 12: ...ting Electrical installation Connection to the 400 V system 4 4 3 Electrical installation 4 3 1 Connection to the 400 V system 4 3 1 1 Connection plan Fig 1 Wiring example S1 Start enable Dashed line options ...

Страница 13: ...5 25 32 Cable cross section mm 6 6 6 10 4 3 1 3 Terminaldata Mains connection Motor connection Inverter VS30407P3 VS30409P5 VS3040013 VS3040016 Rated power kW 3 4 5 5 7 5 Connection X105 Connection type Screw terminal Min cable cross section mm 1 5 Max cable cross section mm 6 16 35 Stripping length mm 9 11 18 Tightening torque Nm 0 5 1 2 3 8 Requiredscrewdriver 0 6 x 3 5 0 8 x 4 0 0 8 x 5 5 Inver...

Страница 14: ...s section mm 6 16 Stripping length mm 10 11 Tightening torque Nm 1 2 3 4 Requiredscrewdriver 0 8 x 5 5 PZ2 Control connections Terminaldescription Relay output PTC input Control terminals Connection X9 X109 X3 Connection type Screw terminal Screw terminal Spring terminal Min cable cross section mm 0 5 0 5 0 5 Max cable cross section mm 1 5 1 5 1 5 Stripping length mm 6 6 9 Tightening torque Nm 0 2...

Страница 15: ...3 2 Connection to the IT system Internal components have earth potential if the IT screws are not removed Consequence the monitoring functions of the IT systemrespond Before connection to an IT system be absolutely sure to remove the IT screws NOTICE TX10 TX10 ...

Страница 16: ...ng resistor B Baud rate CAN node address R d c b a 64 32 16 8 4 2 1 OFF OFF ON OFF ON 20 kbps OF OFF OFF OFF OFF OFF OFF inaktv OFF OFF ON ON 50 kbps Value fromparameter ON OFF OFF ON OFF 125 kbps Node address example aktiv OFF OFF OFF ON 250 kbps OF OFF ON OFF ON ON ON OFF OFF OFF OFF Value fromparameter 500 kbps Node address 16 4 2 1 23 OFF ON OFF OFF 1 Mbps All other combinations Value from par...

Страница 17: ...ntegrated bus terminating resistor R c b a 128 64 32 16 8 4 2 1 Mode Address Bus termina tion Baud rate Parity Modbus node address R c b a 128 64 32 16 8 4 2 1 OFF n c OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Inactive Automatic detection Automatic Value fromparameter ON ON ON Node address example Active Value fromparameter Value from parameter OFF OFF OFF ON OFF ON ON ON Node address 16 4 2 1 23 No...

Страница 18: ...the EN ISO 13849 2 If an external force acts upon the drive axes additional brakes are required Please observe that hanging loads are subject to the force ofgravity The user has to ensure that the inverter will only be used in its intended applicationwithin the specified environmental conditions This is the only way to comply with thedeclared safety relatedcharacteristics With the Safe torque off ...

Страница 19: ...ection type Screw terminal Min cable cross section mm 0 5 Max cable cross section mm 1 5 Stripping length mm 6 Tightening torque Nm 0 2 Requiredscrewdriver 0 4 x 2 5 X1 Specification Unit min typ max SIA SIB LOW signal V 3 0 5 HIGH signal V 15 24 30 Running time ms 3 Input current SIA mA 10 14 Input current SIB mA 7 12 Input peak current mA 100 Tolerated test pulse ms 1 Switch off time ms 50 Permi...

Страница 20: ...instructions and safetyclearances 5 2 Before initial switch on Prevent injury to persons and damage to material assets Check the following before switching on the mains voltage Is the wiring complete and correct Are there no short circuits and earth faults Is the motor circuit configuration star delta adapted to the output voltage of the inverter Is the motor connected in phase direction of rotati...

Страница 21: ... front of the inverter a If the blue RDY LED is blinking and the red ERR LED is off the inverter is ready for operation The controller is inhibited You can now start the drive b If the red ERR LED is lit permanently a fault is pending Eliminate the fault before you carry on with the functionaltest LED status displays RDY LED blue ERR LED red Status meaning off off No supply voltage blinking 1 Hz o...

Страница 22: ...nction for the reversal of rotation direction again X3 DI3 LOW Speed characteristic example DI1 AI1 V 10 0 DI4 Inverter enabled Speed setpoint selection via X3 AI1 active t In this example X3 AI1 is connected to GND t Preset frequency setpoint 1 active DI3 t Invert rotation t fset Hz 50 20 0 20 2 Stop drive 5 s 5 s Preset frequency setpoint 1 20 Hz t 1 Deactivate preset setpoint 1 again X3 DI4 LOW...

Страница 23: ...ulation EN 61800 5 1 Protective measures against Short circuit Earth fault Earth fault strength depends on the operatingstatus Overvoltage Motor stalling Motorovertemperature PTC or thermal contact I xtmonitoring Leakage current 3 5 mA AC 10 mA DC EN 61800 5 1 Observe regulations and safety instructions Mains switching 3 time mains switching in 1 min cyclic without restrictions Starting current 3 ...

Страница 24: ...4 kHz above 45 C reduce rated output current by 2 5 C Operation at a switching frequency of 8 or 16 kHz above 40 C reduce rated output current by 2 5 C Site altitude 0 1000 m a m s l 1000 4000 m a m s l Reduce rated output current by 5 1000m Pollution Degree of pollution 2 EN 61800 5 1 Vibration resistance Transport 2M2 EN 60721 3 2 Operation Amplitude 1 mm Germanischer Lloyd 5 13 2 Hz acceleratio...

Страница 25: ...ed power kW 3 4 5 5 7 5 Mains voltage range V 3 N PE AC 360 V 440 V 45 Hz 55 Hz Operating mode S1 Max ambienttemperature C 45 Switching frequency kHz 4 Rated mains current without mains choke A 9 6 12 5 17 2 20 with mains choke A 6 9 9 12 4 15 7 Rated output current A 7 3 9 5 13 16 5 Motor cable length C2 residential area industrial premises m 20 Weight kg 2 3 3 7 ...

Страница 26: ...23 12 2015 13506330 2 0 01 6211 01r2 CG DRIVES AUTOMATION Mörsaregatan 12 Box 222 25 SE 250 24 Helsingborg Sweden 46 42 16 99 00 Info info se cgglobal com Order order se cgglobal com ...

Отзывы: