CG Drives & Automation, 01-6142-01r0
Mounting
11
2.
Mounting
This chapter describes how to mount the AC drive.
Before mounting it is recommended that the installation is
planned out first.
•
Be sure that the AC drive suits the mounting location.
•
The mounting site must support the weight of the AC
drive.
•
Will the AC drive continuously withstand vibrations
and/or shocks?
•
Consider using a vibration damper.
•
Check ambient conditions, ratings, required cooling air
flow, compatibility of the motor, etc.
•
Know how the AC drive will be lifted and transported.
2.1
Lifting instructions
Recommended for AC drive models
-090 to -250
Fig. 2
Lifting AC drive model -090 to -250
2.2
Stand-alone units
The AC drive must be mounted in a vertical position against
a flat surface. Use the template (in the File archive on our
homepage) to mark out the position of the fixing holes.
Fig. 3
AC drive mounting model 003 to 293
2.2.1 Cooling
Fig. 3 shows the minimum free space required around the
AC drive for the models 003 to 293 in order to guarantee
adequate cooling. Because the fans blow the air from the
bottom to the top it is advisable not to position an air inlet
immediately above an air outlet.
The following minimum separation between two AC drives,
or a AC drive and a non-dissipating wall must be
maintained. Valid if free space on opposite side.
Note: To prevent personal risks and any damage to the
unit during lifting, it is advised that the lifting methods
described below are used.
Load: 56 to 74 kg
(123 - 165 lbs)
Table 5
Mounting and cooling
Frame size
B - F2
[mm(in)]
Frame size
C2, D2, E2, F2 with
IP21
top cover option
[mm(in)]
FLD - FLD,
side-by-side
mm (in)
a
200(7.9)
200(7.9)
b
200(7.9)
200(7.9)
c
0
50(1.97)
d
0
50(1.97)
FLD - wall,
wall-
one side
mm (in)
a
100(3.9)
100(3.9)
b
100(3.9)
100(3.9)
c
0
50(1.97)
d
0
50(1.97)