12
Getting Started
CG Drives & Automation 01-5965-01r1
Fig. 5
Quick setup for dual-pump system (the pumps will start and stop during
setup).
Place both pumps in the pit and
switch the power on.
Both pumps will start running now .
Set the Emotron MASTER DCM
window 71 to 2, see Table 8.
Set the Emotron SLAVE DCM
window 71 to 3.
Continue from here with the
Quick Setup for Single Pump on
the MASTER, see Fig. 4.
Press the
key on the SLAVE.
Continue from here with the
Quick Setup for Single Pump
on the SLAVE, see Fig. 4.