Window Parameters
CG Drives & Automation 01-5965-01r1
05
Measured line voltage.
Symbol V.
0 to 999 V
06
Measured peak power as
percentage of the DCM
measurement range. Press -
and + (in this window)
simultaneously for 3 seconds
to reset the value.
Symbol %.
0 to 125%
0%
07
Total pumping time in hours.
Press - and + (in this window)
simultaneously for 3 seconds
to set the value to 0.
Symbol .
0-99999
0
08
Total number of pump starts.
Press - and + (in this window)
simultaneously for 3 seconds
to set the value to 0.
0-99999
0
09
Parameter lock.
Symbol
. Is displayed when
parameter is locked.
0 to 999
11
Stop level. Symbol %.
0 to 125%
0%
12
Snore margin. Symbol %.
0 to 125%
4%
13
Type of Auto set. Auto set when
the pump is snoring (_)
(No liquid in the pit).
Auto set when the pump is not
snoring (
-
)
(Liquid in the pit).
(
-
) or (_)
(
-
)
Table 8
Window parameters and defaults
Window
Function
Value
Default
Custom
setting
Master Slave
Содержание DCM
Страница 1: ...Emotron DCM Control Unit Instruction manual English...
Страница 2: ......
Страница 6: ...2 Inside the Box CG Drives Automation 01 5965 01r1...
Страница 8: ...4 Safety CG Drives Automation 01 5965 01r1...
Страница 28: ...24 Installation CG Drives Automation 01 5965 01r1...
Страница 36: ...32 Single Pump System Installation CG Drives Automation 01 5965 01r1...
Страница 46: ...42 Protection and Alarm CG Drives Automation 01 5965 01r1...
Страница 54: ...50 Technical Data CG Drives Automation 01 5965 01r1...
Страница 60: ...56 Window Parameters CG Drives Automation 01 5965 01r1...
Страница 62: ...58 Service CG Drives Automation 01 5965 01r1...
Страница 64: ...60 Appendix CG Drives Automation 01 5965 01r1 Fig 19 Dual pump example Figur 16...
Страница 65: ......