52
65 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL(only available at Trans-MiniAUTO.MPU)
67 MAINTENANCE DUE ALARM
69 RESERVED
70 RESERVED
71 RESERVED
72 RESERVED
73 RESERVED
74 RESERVED
75 RESERVED
76 RESERVED
77 RESERVED
78 NO LOADING COMMAND
79 OIL PRESSURE LOW PRE-ALARM
80 OIL PRESSURE LOW SHUTDOWN
81 CONFIGURABLE ANALOG INPUT HIGH PRE-ALARM
82 CONFIGURABLE ANALOG INPUT HIGH SHUTDOWN
This output indicates that the magnetic pick up signal is not sufficient to be used by the unit for speed monitoring.
The alarm can only operate if the speed signal fails to appearduring cranking. It is disabled if ‘multiple attempts to
engage’ is selected. If the MPU fails during engine running this would result in an under speed alarm.
This output indicates that a low temperature warning has occurred.
This output indicates that the generator is now due for maintenance either because it has used all the available
running hours or the periodic maintenance time has expired. To clear the output a maintenance reset must be
performed.
This output indicates that the unit is not calling of the generator contactor or breaker to be closed. Should the unit
close the generator contactor this output will become inactive.
This output indicates that a low oil pressure warning (pre-alarm) has occurred.
This output indicates that a low oil pressure shutdown has occurred.
This output indicates that a high analog input warning (pre-alarm) has occurred.
This output indicates that a high analog input shutdown has occurred.
66 LOW TEMPERATURE
68 GENERATOR CLOSE BREAKER
This output used to close the generator contactor.
This output indicates that the over current pre-alarm has been reached.
This output indicates that the over current trip level has been reached.
This output indicates that the over power pre-alarm has been reached.
This output indicates that the over power shutdown has been reached.
This output indicates that the over speed warning (pre-alarm) has occurred.
This output indicates that the over speed shutdown has occurred.
83 OVER CURRENT PRE-ALARM
84 OVER CURRENT ALARM
85 OVER POWER PRE-ALARM
86 OVER POWER SHUTDOWN
87 OVER SPEED PRE-ALARM
88 OVER SPEED SHUTDOWN