3.4 Connection of Device Supply Voltage Input
16
Universal Supply
Voltage Connection
Low Voltage 24 V
W
Supply Voltage Input
100 - 240 V
V
(-15%;+10%) 50/60Hz
24V
V
(-15%;+10%) 50/60Hz
Or 24V
Z
(-15%;+10%)
Supply Voltage
23
N
L
24
N
t
1
o
e
-
Y
23
L
24
Y
Power
Supply
Switch
c
c
a
a
External
Fuse
(1 A
V
T)
External
Fuse
(24V
V
: 1 A
V
T)
(24V
Z
: 1 A
Z
T)
Note-2
N
Supply Voltage
N
o
te
-1
Power
Supply
Switch
F
u
s
e
F
u
s
e
N
o
te
-3
N
o
te
-3
c
c
c
Note-1 :
There is an internal 33R
W
fusible flameproof resistor in 100-240 V
V
50/60Hz supply
voltage input
There is an internal 4R7
W
fusible flameproof resistor in 24V
V
50/60Hz , 24V
Z
supply voltage
input
Note-2 : “L”
is ( + ) ,”
N”
is ( - ) for 24V
Z
supply voltage
Note-3 :
External fuse is recommended.
Make sure that the power supply voltage is the same indicated on the
instrument.
Switch on the power supply only after that all the electrical connections have
been completed.
Supply voltage range must be determined in order. While installing the unit,
supply voltage range must be controlled and appropriate supply voltage must
be applied to the unit. Controlling prevents damages in unit and system and
possible accidents as a result of incorrect supply voltage.
There is no power supply switch on the device. So a power supply switch must
be added to the supply voltage input. In accordance with the safety regulations,
the power supply switch shall bring the identification of the relevant
instrument.Power supply switch shall be easily accessible by the user.
Power switch must be two poled for seperating phase and neutral. On/Off
condition of power switch is very important in electrical connection. On/Off
condition of power switch must be signed for preventing the wrong connection.
If an external fuse is used, it must be on phase connection in
V
supply input.
If an external fuse is used, it must be on (+) line connection in
Z
supply input.
The instrument is protected with an internal fuse (Please refer to Note1 for
information). In case of failure it is suggested to return the instrument to the
manufacturer for repair.