5. DISPLAY SIGNALINGS
08
USER
MANUAL
TEMPERATURE CONTROLLER
STORM
ST
101
2HP
Sensor Error: Disconnected or damaged.
Control functions turned off.
Manual activation of the defrost process.
Manual activation of the cooling process.
Blocked functions.
Activate function blocking.
NFC Blocked, parameters transmitted by the APP
have not been saved.
Er1
OFF
dFr On
dFr OFF
LOC
LOC On
nFC LOC
Message
Description
Parameters transmitted by the APP are corrupted,
not saved.
NFC not initialized. Out of operation.
Delay when starting the controller.
Cooling mode turned on.
Heating mode turned on.
Parameters successfully saved.
nFC REJ
nFC Er4
dEL
rEF
Hot
nFC Sto
Message
Description
TABLE 4
6. DESCRIPTION OF PARAMETERS AND FACTORY VALUES
P02 – Desired temperature (Setpoint):
It is the value set for temperature control, where the load supply output is turned off.
-50
4
200
ºC
Standard value
Minimum
Maximum
Unid
Operating mode
Heating | Cooling
P03 – Indication shifting (Offset):
It is the value of the compensation for temperature differences presented by the controller.
-5
0
5
ºC
Standard value
Minimum
Maximum
Unid
Operating mode
Heating | Cooling
0,1
1
20
ºC
Standard value
Minimum
Maximum
Unid
Operating mode
Heating | Cooling
P04 and P05 – Minimum/Maximum setpoint allowed to the user (P02):
It is the temperature range defined for the user.
-50
-50
200
ºC
Standard value
Minimum
Maximum
Unid
Operating mode
Heating | Cooling
-50
75
200
ºC
Heating | Cooling
P06 – Control differential (hysteresis):
It is the temperature difference (hysteresis) where the controller will operate. Examples:
Cooling
P02 = 4ºC
Compressor OFF
5ºC
Compressor ON
P06 = 1ºC
P04
P05
ºC
Heating
25ºC
Heater ON
P02 = 30ºC
Heater OFF
P06 = 5ºC
P04
P05
ºC