background image

The Ductless Split System of Choice

Made in Rome, New York, USA

1

tion  on  “Maximum  Range  vs.  Limited  Range  Heat

Pumps”).

• 

Circuit Numbering:

9 (9,000 BTU/h)

2 (12,000 BTU/h)

5 (15,000 BTU/h)

8 (18,000 BTU/h)

4 (24,000 BTU/h)

3 (30,000 BTU/h)

0 (No Compressor)

• The MC/MH2 is only available in three capacities

and only in dual zones. This means you can order any

combination of two circuits in either the MC or MH

units. The capacities are 9, 2, and 5 (as noted above).

• With an MC/MH4, you cannot mix and match any

15,000 BTU/h or 30,000 BTU/h unit with other ca-

pacities in a heat pump (ex: An MC4 2203 is a good

combination while an MH4 2203 is not).

• The only capacities available in 4 zones are 9,000,

12,000,  and  15,000  BTU/h  circuits.  If  an  18,000,

24,000, or 30,000 BTU/h capacity is incorporated, the

maximum number of circuits falls to three (3). A unit

model number with three (3) circuits will have a “0”

in the model number (ex: MC4 9208). If the capaci-

ties required are any combination of 18,000, 24,000,

or 30,000 BTU/h, the number of circuits equals two

(2) and the unit model number will have two zeros

(ex: MC4 0803).

• The MC and MH units utilize separate refrigeration

circuits that are independent from each other. Each

circuit  has  its  own  compressor  and  control  circuit.

There is one condenser fan that is operating continu-

ously when one or all of the circuits are functioning.

If the heat pump (MH) model is selected, the user can

run one circuit in cooling mode and one in heat mode

if desired.

• Air handlers that can be matched with the preceding

condensing units are CAH, CSP/CHP, FSP/FHP, TBH,

and WHP.

SITE INFORMATION/REQUIREMENTS

• Do not install units in high traffic areas, drip lines of

roofs, or overhangs.

• EMI condensers require a minimum 12” intake air

clearance and 48” discharge air clearance for proper

unit operation. We also recommend a minimum 12”

clearance to the side and 48” to the front and rear be-

GENERAL INFORMATION

This guide is intended for use by EMI contractors,

distributors,  installers,  representatives,  and  service

technicians to gain a better understanding of EMI Ductless

Split Systems.

This guide will supplement the information found in

the 

Installation, Operation,  & Maintenance Guide

 and the

Specifications & Performance Guide

 for your unit. EMI also

publishes 

Policy Bulletins

 pertaining to specific installation

and service issues. These bulletins can be found in the full

line catalog and topics include (but are not limited to):

• Equipment Matching

• Labor Allowances

• Return Policies

• Run Length/Lift

• Tubing Size Requirements

• Warehousing Charges

EMI recommends technicians and installers read this

material prior to installing or servicing an EMI Split Sys-

tem. Any questions can be directed to our customer service

department at (315) 336-3716.

SYSTEM DESIGN

EMI  manufactures  two  series  of  straight-cool

condensing units and limited range heat pumps that can be

matched with any corresponding size EMI-manufactured air

handler.

America Series Single Zone Outdoor Units*

• SCC: Models 9-36 (straight cool)

• CCB: Models 42-48 (straight cool)

• SHC: Models 9-36 (heat pump)

• CHD: Models 42-48 (heat pump)

America Series Multi-Zone Outdoor Units**

• MC2/MC4: 2-4 Zone (straight cool)

• MH2/MH4: 2-4 Zone (heat pump)

* Single Zone indicates that each unit has one compressor to be

connected to a single air handler.

** Multi-zone describes a unit  with more than  one compressor
for more than one air handler.

EMI manufactures the most extensive line of multi-

zone circuit options in the Ductless Split industry. Due to

running changes and advances, unit decoding and option

availability can become confusing.

The  following  will  answer  some  Frequently Asked

Questions regarding EMI multi-zone condenser options:

• The MH unit is a 

limited range

 heat pump (see sec-

DUCTLESS SPLIT SYSTEM

Service and Technical Guide

P/N 240-2985, Rev. 1.2 [07/01]

CLICK ANYWHERE on THIS PAGE to RETURN to HVAC MANUALS & REPAIR GUIDES at InspectApedia.com

Содержание AmericaSeries LLC-09

Страница 1: ...the side and 48 to the front and rear be GENERAL INFORMATION This guide is intended for use by EMI contractors distributors installers representatives and service technicians to gain a better underst...

Страница 2: ...ndenser is equipped with low ambient fan control for cooling The fan will remain off while in cooling mode until the condenser pressure reaches 275psi The fan will then energize and run until the cond...

Страница 3: ...ng conditions are met properly see EMI Policy Bulletin 910503 All equipment capacities must have the same BTU h rating and efficiency rating SEER A transformer must be added to the outdoor unit if not...

Страница 4: ...ave a P trap installed at the base to facilitate oil return when the condenser is above the evaporator Fig 1 When the evaporator is installed above the compres sor the trap will prevent the flow of li...

Страница 5: ...ft of 4 feet from the bottom of the unit NOTE Before completing installation test pump action EMI offers external pumps for installations that re quire more than 4 feet of lift SYSTEM TROUBLESHOOTING...

Страница 6: ...ct inside the fittings for any for eign particles that may have collected there The for eign particles can consist of pieces of valves wind ings or thermal overload particles and other related items n...

Страница 7: ...ession fittings Ethylene or propylene is recommended Bleed air from system prior to start up Units are equipped with a standard air bleeder on the highest point of the unit piping CAUTION Disconnect p...

Страница 8: ...NTRO L B AT T E R IE S INCL UDE D POWER ON OFF Button INFRA RED SENSOR T EMP SET POINT DOWN Button T EMP SET POINT UP Button LCD Display HEAT OPERAT ION Indicator FAN LOW Indicator FAN HIGH Indicator...

Страница 9: ...Y wire When the air handler is calling for cooling 24v can be measured between terminals wires Y and C NOTE Most condenser manufacturers do not supply low volt transformers with their condensers When...

Страница 10: ...ereby cutting the Y signal to the condenser This will prevent the evaporator from generating more condensation and spilling out of the unit FREEZE PROTECTION The indoor fan coil unit is protected in t...

Страница 11: ...ton in Place the setpoint tem perature above the room temperature The compressor will start heating and run as long as the setpoint is above the room temperature Some EMI heat pump condensers are equi...

Страница 12: ...ar may not work for a unit manufactured in a dif ferent model year NOTE EMI does not stock or recommend electric heat add on kits for field installation It is critical that if you can foresee the need...

Страница 13: ...______________________________________ Subcooling ___________________________________________________________ Suction Temperature at Compressor _____________________________________ Voltage Running __...

Страница 14: ...a F e g r a h C m e t s y S l a t o T 2 1 W C L z o 5 2 0 1 5 2 0 5 z o 3 z o 6 z o 3 1 z o 0 3 z o 3 3 z o 6 3 z o 3 4 LCC 12 p a v E l e d o M e n i L T F G H C e n i L h t g n e L t f l a t o T t...

Страница 15: ...r o t c a F e g r a h C m e t s y S l a t o T 2 1 P H C P S C 2 1 P H W P S W 2 1 P H F P S F 2 1 H C B T 2 1 H A C z o 5 2 0 1 5 2 0 5 z o 3 z o 6 z o 3 1 z o 5 6 2 z o 9 2 z o 2 3 z o 9 3 p a v E l...

Страница 16: ...L t f l a t o T t s u j d A y r o t c a F e g r a h C m e t s y S l a t o T 2 1 P H C 2 1 P H F 2 1 P H W 2 1 H B T 2 1 H A C z o 5 2 0 1 5 2 0 5 z o 3 z o 6 3 1 z o z o 2 4 z o 5 4 z o 8 4 z o 5 5 S...

Страница 17: ...e g r a h C m e t s y S l a t o T 4 2 P H C P S C 4 2 P H F P S F 4 2 P H W P S W 4 2 H C B T 4 2 H A C 6 5 0 1 5 2 0 5 z o 6 z o 4 1 z o 8 2 z o 1 4 z o 7 4 z o 5 5 z o 9 6 MH 18 l e d o M p a v E e...

Страница 18: ...5 1 1 0 8 2 0 2 2 5 7 5 7 1 5 6 2 0 6 2 5 2 1 5 2 2 0 0 2 0 8 0 7 1 0 6 2 0 6 2 5 2 1 5 8 1 0 8 1 5 8 0 6 1 5 5 2 0 4 2 5 2 1 5 8 1 0 6 1 0 9 5 5 1 5 4 2 0 3 2 0 1 1 5 4 1 0 6 1 5 9 0 5 1 5 4 2 0 2 2...

Страница 19: ...in Degrees F p m e T D O F s e e r g e D 9 0 2 1 5 1 8 1 4 2 0 3 6 3 5 6 5 4 3 5 8 2 0 1 2 5 9 1 5 4 2 0 2 2 0 3 2 0 7 0 7 2 0 7 2 0 1 2 0 9 1 0 4 2 5 3 2 0 3 2 5 7 5 1 2 0 6 2 0 1 2 0 9 1 0 4 2 0 4...

Страница 20: ...20 EMI Products are subject to ongoing development Products Specifications may change without notice O L Over Load...

Страница 21: ...ump Pending Slv Brg Whl C 265V 60Hz E X Special 220 240V 50Hz F A Standard 0 Standard B No Expansion KW X Special C Open 208V 230V 265V D Open NONE 0 0 Unit Mount w Trans Mechanical E Aeroquip 2 50 3...

Страница 22: ...C 1 2 D A 0 0 0 0 A A 0 A A SCC C Straight Cool 0 Standard SHC H Heat Pump A Z A Standard 9 000 BTU 09 A Standard 12 000 BTU 12 X Special 15 000 BTU 15 0 Painted Coil No Grille Std 115V 60Hz A A Coat...

Страница 23: ...____________________________________________ __________________________________________________________________________________________ ________________________________________________________________...

Страница 24: ...almaintenance Damage or repairs required as a consequence of faulty installation or application by other Failure to start due to voltage conditions blown fuses open circuit breakers or other damages d...

Отзывы: