Chapter9. Troubleshooting and Countermeasures
The below table listed EM15 inverter all types of faults possibly occurs. Before contacting manufacturer for
technical support, you can first determine the fault type through following table description and records your done
treating process and phenomena. if the fault can not be resolved, please seek for the manufacturer service support.
Troubleshooting table
Fault code
Display
Possible reason
Countermeasures
Inverter unit
protection
Err01
1, The inverter output circuit short
circuit
2, the motor and inverter wiring is
too long
3, the module overheating
4.The inverter wiring is loose
5, The circuit board abnormal
6, inverter module exception
1, Excluding the external fault
2, Install the reactor or output filter
3, Check the air duct is blocked;
4, Plug all the cable
5, Seek technical support
Over current in
acceleration
Err02
1, Motor to ground short circuit
2, Not perform auto tuning
3, The acceleration time is too short
4, Torque boost is not appropriate
5, The grid voltage is low
6, Loading suddenly in acceleration
7, The using Inverter capacity (rated
power is small
1, Excluding the external fault
2, Perform motor ID auto tuning
3, Increase the acceleration time
4, Adjust the torque boost or V / F
curve
5, Adjust voltage of power supply to
normal
6, Adjust the load
7, Select big power inverter instead
Over current in
deceleration
Err03
1, Output short circuit or output to
ground
2, No performance ID auto tuning
for carrying vector control
3, The deceleration time is too short
4, The voltage is low
5, Loading suddenly when
deceleration
6, No installing of brake unit and
brake resistor
1, Excluding the external fault
2, Perform motor ID auto tuning
3, Increase the acceleration time
4, Adjust voltage of power supply to
normal
5, Cancel the suddenly adding load
6, Install braking unit or braking
resistor
Over current in
constant speed
running
Err04
1, The inverter output short circuit
or phase to ground
2, No performance ID auto tuning
for carrying vector control
3, The voltage of grid is low
4, Whether there is a sudden load in
running
5, The using Inverter capacity (rated
power is small
1, Excluding the external fault
2, Perform motor ID auto tuning
3, Cancel the sudden loading
4, Cancel the suddenly adding load
5. Select big power inverter instead