5.Description of Function Codes
EM12 User's Manual
66
Thousand's digit: VDO4. 0, 1 (same as unit's digit)
Ten thousand's digit: VDO5. 0, 1 (same as unit's digit)
VDO functions are similar to the DO functions on the control board. The VDO can be used together with VDIx to
implement some simple logic control.
If VDO function is set to 0, the state of VDO1 to VDO5 is determined by the state of DI1 to DI5 on thecontrol
board. In this case, VDOx and DIx are one-to-one mapping relationship.
If VDO function is set to non-0, the function setting and use of VDOx are the same asDO in group b4.
The VDOx state valid can be set in b7-21. The application examples of VDIx involved the usage of VDOx, and
please see these examples for your reference.
5.9 Group b8: AI/AO Correction
b8-00
Ideal voltage of AI1 calibration 1
Default
2.000V
Setting Range
0.500~4.000 V
b8-01
Sampling voltage of AI1 calibration 1
Default
2.000V
Setting Range
0.500~4.000 V
b8-02
Ideal voltage of AI1 calibration 2
Default
8.000V
Setting Range
6.000~9.999 V
b8-03
Sampling voltage of AI1 calibration 2
Default
8.000V
Setting Range
6.000~9.999 V
b8-04
Ideal voltage of AI2 calibration 1
Default
2.000V
Setting Range
0.500~4.000 V
b8-05
Sampling voltage of AI2 calibration 1
Default
2.000V
Setting Range
0.500~4.000 V
b8-06
Ideal voltage of AI2 calibration 2
Default
8.000V
Setting Range
6.000~9.999 V
b8-07
Sampling voltage of AI2 calibration 2
Default
8.000V
Setting Range
6.000~9.999 V
b8-08
Ideal voltage of AI3 calibration 1
Default
2.000V
Setting Range
0.500~4.000 V
b8-09
Sampling voltage of AI3 calibration 1
Default
2.000V
Setting Range
0.500~4.000 V
b8-10
Ideal voltage of AI3 calibration 2
Default
8.000V
Setting Range
6.000~9.999 V
b8-11
Sampling voltage of AI3 calibration 2
Default
8.000V
Setting Range
6.000~9.999 V
b8-12
Ideal voltage of AO1 calibration 1
Default
2.000V
Setting Range
0.500~4.000 V
b8-13
Measured voltage of AO1 calibration 1
Default
2.000V
Setting Range
0.500~4.000 V
b8-14
Ideal voltage of AO1 calibration 2
Default
8.000V
Setting Range
6.000~9.999 V
b8-15
Measured voltage of AO1calibration 2
Default
8.000V
Setting Range
6.000~9.999 V
b8-16
Ideal voltage of AO2 calibration 1
Default
2.000V
Setting Range
0.500~4.000 V
b8-17
Measured voltage of AO2 calibration 1
Default
2.000V
Setting Range
0.500~4.000 V
b8-18
Ideal voltage of AO2 calibration 2
Default
8.000V
Setting Range
6.000~9.999 V
b8-19
Measured voltage of AO2 calibration 2
Default
8.000V
Setting Range
6.000~9.999 V