20
View from below (maximum terminal assignment, specifications
in mm)
When the devices are
tested, the voltage circuits
are disconnected by a path
separator.
Remove the path separa-
tor again when resuming
normal operation!
DANGER
Improper installation endangers life and health, and can lead to
malfunctions and material damage!
The voltage connections in the meter are not fuse-protected, and are
connected directly to the measuring voltage potential.
y
The connecting paths must be fuse-protected as per the applicable
technical regulations and in accordance with the current specifica
-
tion on the meter’s name plate.
y
Use an overcurrent protection device rated for a maximum of 100 A
as per the applicable Technical Connection Rules for Power Instal-
lations (e.g. selective main line circuit breaker) upstream of a meter
with direct connection.