26
Meter operation
Display control
The following applies to operation by means of the call-up button:
y
K
Pressing briefly (t < 2 s):
• Moves to the next list value, menu item or setting value
• Activates the illumination of the display if the meter is equipped in
this way
y
L
Pressing for a long time (2 s ≤ t < 5 s):
• Activates the currently displayed menu item
•
Confirms the adoption of the changed settings
y
Pressing for a longer time (t ≥ 5 s):
• The display returns to the standard operating display at any time
Error display
When an error occurs, it appears on the standard operating display.
In case of multiple errors, the sum of the relevant error codes is displayed
in hexadecimal format.
Error code
Meaning
00000001
Program code faulty
00000002
Parametrisation data faulty
00000004
Editing data faulty
00000008
Data backup faulty
00000010
Synchronisation data faulty
If an error is displayed, the meter data must no longer be used
for billing.
Operation of the device can be affected.
Start list
Once voltage is applied, the display shows the firmware version number
and the firmware checksum for 5 s each. It is not possible to operate the
meter. Then the standard operating display appears.