16.0 Trouble Shooting
With the Diagnostic Module, a technician is alerted to following type of conditions :
Discharge Line Temperature Overlimit
Ambient Sensor Failure
Mid Coil Temperature Sensor Failure
Discharge Line Temperature Thermistor Failure
High Pressure Cut Out
Compressor Over Current
Compressor Incorrect Phase Sequence
Compressor Voltage Imbalance
System Liquid Floodback
Troubleshooting for a ZX Condensing Unit is not very different form that for any other type of unit
except that with the feedback from the Diagnostic Module , the technician gets to the core of the
issues much quicker. These are CDU related conditions that can also give the technician some
idea about the condition of the system by using some basic refrigeration troubleshooting tables
( but not limited to these) as below with a basic gauge manifold :
D
S
48
Possible Causes/Effects
ischarge Pressure
Low
Refrigerant Shortage
Dirty Evaporator
Iced-up Evaporator
Low Superheat Setting at TXV
Restriction in Refrigeration system
High
Front Seated Receiver Rotalock Valves
Lack of Ventilation around Unit
Refrigerant Overcharge
Presence of Non-Condensibles
High Ambient Temperatures
uction Pressure
Low
Oversized Unit
Undersized Evaporator
Liquid Flashing in Liquid Line
High
Oversized Evaporator
Excessive Airflow over Evaporator
Refrigerant Overcharge
Содержание ZX
Страница 1: ...1 ZX OUTDOOR REFRIGERATION CONDENSING UNIT USER MANUAL Emerson Climate Technologies Suzhou Co Ltd ...
Страница 8: ...Fig 4 The Defrost Module Fig 5 The Diagnostic Module now available without Buzzer 8 ...
Страница 21: ...ZX200 300 400 Single Fan Units 21 ...
Страница 22: ...ZX500 600 750 Dual Fan Units 22 ...
Страница 43: ...Fig 23 Diagnostic Module and Defrost Module connected to the E2 Unit Controller 43 ...
Страница 51: ...Addendum 17 2 ZX Wiring Diagram 51 ...
Страница 52: ...Addendum 17 3 Capacity kW at 50Hz for Refrigerant R22 52 ...
Страница 54: ...54 ...