YarwaY

 9200 SerieS ArC

®

 VAlVeS 2", 3" And 4"

InstallatIon and maIntenance InstructIons

Before installation these instructions must be fully read and understood

© 2017 emerson. All rights reserved.

valves.emerson.com

VCIOM-03341-EN 17/05

engineering doc. #972562 rev. A

OpEratION

Flow through the check valve overcomes the 
spring force to open the main check valve 
element. When the disc lifts in response to 
an increase in main flow, the bypass flow is 
decreased as the port openings in the disc stem 
begin to close. Conversely, as the pump flow is 
reduced, the check disc moves downward and 
at a designated point starts to uncover the disc 
stem ports allowing bypass flow to begin.
The sizing of the main check/trim is such that 
the bypass flow starts before the main flow 
drops below the minimum pump flow specified. 
The combined main and bypass flows provide 
a total greater than the minimum pump flow 
requirement.
Bypass flow enters the disc stem passage 
through the slots and the round ports and 
around the annulus in the bypass bushing. it 
then continues through the bypass where the 
helix element conditions the flow at the valve 
bypass outlet. The recirculation flow rate is 
controlled by the disc slot sizing. Occasionally 
higher pressure applications may require the 
use of a Back Pressure regulator (BPr) in the 
bypass line for proper pressure letdown.

GENEral

These sizes in the 9200 ArC

®

 (Automatic 

recirculation Control) valve series are designed 
to provide protection for low to moderate 
pressure (ASMe/AnSi 150 and 300 Class) 
centrifugal pumps against overheating and 
possible unstable operation during low load 
periods. The valve functions simultaneously 
as (1) a check valve - to prevent reverse flow 
through the pump and as (2) a bypass control 
valve - to maintain the minimum required 
pump flow and provide pressure letdown.

Содержание Yarway 9200 Series

Страница 1: ...he combined main and bypass flows provide a total greater than the minimum pump flow requirement Bypass flow enters the disc stem passage through the slots and the round ports and around the annulus in the bypass bushing It then continues through the bypass where the helix element conditions the flow at the valve bypass outlet The recirculation flow rate is controlled by the disc slot sizing Occas...

Страница 2: ...rmal main flow and minimum flow requirements could result in unsatisfactory performance If operating conditions have changed contact Yarway modifications may be required prior to installation Remove all packing material Place the valve on wooden blocks with the flow arrow pointed down Push the disc from its seat and flush away any packing materials with compressed air or high pressure water The di...

Страница 3: ...en the upper stop jacking screws 10 relieving spring compression until the upper stop is free Remove the upper stop inspect and replace gasket 8 and snubber seal 9 3 Remove the spring 7 and inspect for damage 4 Lift the disc assembly until it clears the valve body Inspect the disc stem slot surfaces and snubber seal 9 for damage or excessive wear Note if substantial flow and pressure related damag...

Страница 4: ...th ASTM A747 Grade CB7Cu 1 17 4 PH Cast Condition H900 J92180 seat ring 2 Upper stop ASTM A216 WCB 3 Orifice 18 8 4 2 Disc assembly ASTM A351 type CF8M 5 Flow conditioner ASTM A351 type CF8M 6 Bypass bushing ASTM A747 Grade CB7Cu 1 17 4 PH Cast Condition H900 J92180 7 2 Spring AISI 316 stainless steel 8 1 2 Gasket Sigraflex BP Graphite 9 1 2 Snubber seal Variseal Carbon filled TFE 10 Screw AISI 31...

Отзывы: