26 • XEV22D I&O Manual
026-1206 Rev 3 13-DEC-2012
20 Standard Values
NOTE: For viewing and adjusting setpoints, refer to: Section 9.2., To See the Setpoint and Section 9.3., To
Modify the Setpoint.
Label
Description
Range
Default
Level
Fty
Kind of gas
R22, 134, 404, 407, 410, 507, CO2
404
Pr2
PEo
Probe error opening percentage
0 to 100%
50
Pr2
PEd
Probe error delay before stopping regulation
0 to 239 sec - On
On
Pr2
tEU
Type of stepper motor
uP
–
bP
bP
Pr2
tEP
Automatic valve configuration
0 to 10
1
Pr2
LSt
Minimum number of steps
0 –
Ust
See
tEP
Pr2
Ust
Maximum number of steps
LSt
– 800 * 10
See
tEP
Pr2
Sr
Step rate
10 to 600 step/s
See
tEP
Pr2
CPP
Current per phase (only bipolar valves)
0 to 100 * 10mA
See
tEP
Pr2
CHd
Holding current per phase (only bipolar valves)
0 to 100 * 10mA
See
tEP
Pr2
oPE
Start opening percentage
0 to 100%
85
Pr2
SFd
Start function duration
0.0 to 42.0 min: tens of seconds
1.3
Pr2
Sti
Stop regulation interval
0.0 to 24.0 hr: tens of minutes
0
Pr2
Std
Stop duration
0 to 60 min
0
Pr2
MnF
Maximum opening percentage
0 to 100%
100
Pr2
FOP
Forced opening time-out
0 to 100% -
not used
not used
Pr2
PI PARAMETERS (For trained staff use only)
Pb
Proportional band
0.1 to 50.0°C/ 1 to 90°F
10.0
Pr2
rS
Band offset
-12.0 to 12.0°C/ -21 to 21°F
0.0
Pr2
inC
Integration time
0 to 255 sec
120
Pr2
PROBE PARAMETERS
tPP
Type of pressure transducer
420 - 5V- LAn
420
Pr2
LPP
Enable pressure probe sending in LAN
n
to
Y
n
Pr2
PA4
Probe value at 4mA or at 0V
(related to
PrM
parameter)
-1.0 bar/ -14 PSI
-0.5
Pr2
P20
Probe value at 20mA or at 5V
(related to
PrM
parameter)
PA4
to 50.0 bar/ 725 PSI
11.0
Pr2
OPr
Pressure probe calibration
-12.0 to 12.0 bar/ -174 to 174 psi
0
Pr2
ttE
Type of temperature probe
PtM
to
ntC
PtM
Pr2
otE
Temperature probe calibration
-12.0 to 12.0°C/ -21 to 21°F
0
Pr2
DIGITAL INPUTS
Table 20-1 -
XEV22D Standard Parameter Values