6 – 3
VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391STG
Slide Valve Actuators communicate problems discovered by internal diagnostics via LED blink codes. Only one blink
code is displayed, even though it is possible that more than one problem has been detected.
Flash Pattern
Meaning
*=ON
_=OFF
*_*_*_*_*_*_*_*_*_*_*_
Calibration step 1
*___*___*___*___*___
Calibration step 2
*__*________________
This indicates a zero span. This error can only occur during calibration. The typi-
cal cause is forgetting to move the actuator when setting the upper limit of the
span. If this is the case, press the blue button to restart the calibration proce-
dure. This error can also occur if either or both of the slotted optocouplers are
not working. If this is the case, the slide valve actuator will have to be replaced.
The operation of the slotted optocouplers is tested as follows:
1. Manually rotate the motor shaft until the aluminum photochopper fence is
not blocking either of the optocoupler slots.
2. Using a digital multi-meter, measure the DC voltage between terminal 3 of
the small terminal block and TP1 on the circuit board (see Note 1). You should
measure between 0.1 and 0.2 Volts.
3. Next, measure the DC voltage between terminal 3 and TP2 on the circuit
board. You should measure between 0.1 and 0.2 Volts.
*__________________
This indicates a skipped state in the patterns generated by the optocouplers as
the motor moves. This error means that the slide valve actuator is no longer
transmitting accurate position information. The actuator should be recalibrated
as soon as possible. This code will not clear until the actuator is recalibrated.
This code can be caused by:
1.
The motor speed exceeding the position sensors ability to measure it
at some time during operation. A non-functioning motor brake is usually to
blame.
2.
The actuator is being operated where strong infrared light can falsely
trigger the slotted optocouplers, such as direct sunlight. Shade the actuator
when the cover is off for service and calibration. Do not operate the actuator
with the cover off.
Section 6 • Troubleshooting
Table 6-2. Slide Valve Actuator LED Blink Codes* (1 of 2)
Содержание Vilter VSG
Страница 1: ...VSG VSSG compressor unit Installation operation maintenance manual FOR UNITS BUILT AFTER JULY 1 2013 ...
Страница 2: ......
Страница 10: ...Blank TOC VSG VSSG Installation Operation and Maintenance Manual Vilter Emerson 35391STG ...
Страница 104: ...6 8 Blank VSG VSSG Installation Operation and Maintenance Manual Vilter Emerson 35391STG ...
Страница 109: ...C VSG VSSG Installation Operation and Maintenance Manual Vilter Emerson 35391STG Appendix C Recommended Header Piping ...
Страница 111: ......