MicroVission Retrofit Instructions • 35391MVRF
Black: 120 VAC
White: Neutral
Green: Ground
3.0 Field Wiring
Figure 15. 120 VAC Connection to MicroVission
WARNING
Ensure power/control switches are in the off position
and all power are disconnected. Follow lockout
procedure prior to working on electrical equipment.
Failure to comply may result in serious injury or death.
NOTICE
Always follow your employer’s electrical safety
program and NFPA 70E when working around and in
energized equipment – this manual is not a substitute
for NFPA 70E.
NOTICE
Before applying power to the MicroVission control
panel, all wiring to the panel should be per the
National Electrical Code (NEC). Specifi cally check for
proper voltage and that the neutral is grounded at
the source. An equipment ground should also be run
to the panel.
CAUTION
Do not route A/C and D/C wires together, this will
cause Electromagnetic Interferance (noise). Failure to
comply may result in damage to equipment.
3.1 Power and Input/Output Wiring at the Panel
Step 1.
Connecting 120VAC power: take a look at the wires on the right hand side of panel, run through DIN rail to
breaker CB1. This corresponds to the power distribution hookup on SHEET 10 of the drawing set, see Figure 14.