12
MicroVission Retrofit Instructions • 35391MVRF
Step 10.
Install the 4-20mA current transmitter to sense the amperage at the motor terminal box, and connect to the
analog input at the MicroVission panel, see Figure 14.
NOTE
The Keypad and VILTech Micro-controllers did not have
an amperage input, and the Vantage used a different
type CT, so the acquisition of current transmitter (VPN
3669CT) is imperative to work with the MicroVission
panel. This transmitter is contained in retrofi tting kit
KT24X20MV, see Table 2.
Step 11.
Go to section 3.0 for wiring instructions.
Figure 14. Connection of 4-20mA Current Transmitter (Sensor)
Содержание Vilter MicroVission