Indicator light scenarios
Table 2-1:
Power
indicator
light
Field
connection
indicator light
Scenarios
Normal scenarios
Green
Green
The USB Fieldbus Interface is connected to an externally
powered segment and is able to communicate.
Amber
Green
The USB Fieldbus Interface is providing power to a fieldbus
segment and is able to communicate.
Other scenarios
Off
Off
The USB Fieldbus Interface is not connected to a powered
computer.
-OR-
The USB Fieldbus Interface is connected to a computer but
the computer power is off.
-OR-
The USB FF HSE Server is not running on the connected
computer.
Green
Off
The USB Fieldbus Interface is not connected to a powered
segment.
-OR-
The USB Fieldbus Interface is connected to a powered
segment with the wrong polarity.
Off
Green
The USB Fieldbus Interface is connected normally to a
powered segment but the USB FF HSE Server is not running.
Amber
Red
The USB Fieldbus Interface is providing power but a short
circuit has been detected on the field connection.
Amber
Off
The USB Fieldbus Interface is providing power and
connected to an already powered fieldbus segment with
reverse polarity.
Amber
Amber
The USB Fieldbus Interface is providing power to a fieldbus
segment and the load on that segment has exceeded its
limit.
User's Manual
May 2014
8
Содержание USB Fieldbus Interface
Страница 1: ...User s Manual AW7060MNL Rev 2 May 2014 USB Fieldbus Interface User s Manual ...
Страница 13: ...Emerson DTM Library installation Figure 3 3 5 Click Close when done May 2014 User s Manual 13 ...
Страница 42: ...Edit device parameters Figure 6 12 User s Manual May 2014 42 ...
Страница 53: ...Windows Device Manager Figure D 3 May 2014 User s Manual 53 ...