background image

V Series

Instruction Manual

D103666X012

January 2015 - Rev. 00

TM

Summary

Introduction  ........................................................................ 

1

SEP Statement  .................................................................. 

1

P.E.D. Categories and Fluid Group  ................................... 

2

Characteristics  ................................................................... 

2

Labelling  ............................................................................ 

2

Overpressure Protection ....................................................

 3

Transport and Handling  .....................................................

 3

Atex Requirements  ............................................................

 3

Operation  ........................................................................... 

3

Dimensions and Weights  ................................................... 

4

Installation  ......................................................................... 

5

Startup  ............................................................................... 

5

Setting  ............................................................................... 

5

Shutdown ........................................................................... 

6

Periodical Checks  .............................................................. 

6

Maintenance  ...................................................................... 

6

Spare Parts ........................................................................ 7

Troubleshooting  ................................................................. 

7

Parts Lists  .......................................................................... 

8

Schematic Assemblies ....................................................... 

9

INTrODuCTION

Scope of manual

This manual provides instructions for installation, startup, 

maintenance and spare parts ordering for the V Series  

spring-loaded relief valves.

This product has been designed to be used with fuel gases of 

1st and 2nd family according to EN 437, and with other non 

aggressive and non fuel gases. For any other gases, other 

than natural gas, please contact your local sales agent.

SEP STaTEmENT

Emerson Process Management declares this product (V/50 

and V/20-2) conforms to Pressure Equipment Directive 

(PED) 97/23/EC Article 3 section 3 and was designed 

and manufactured in accordance with sound engineering 

practice (SEP).

Per Article 3 section 3, this “SEP” product must not bear the 

CE marking. 

Product Description 

The V Series are spring-loaded automatic type relief valves.

They are used in reduction, distribution and conveying 

stations using suitably filtered natural gas.

They can also be used for air, propane, butane, LPG, city 

gas, nitrogen, carbon dioxide.

The following versions are available:

 

V/50 and V/60 :

 for very low pressure applications

 

V/51 and V/61 :

 for low pressure applications

 

V/52 and V/62 :

 for middle pressure applications

 

V/20-2 :

 for high pressure applications 

All standard gas pressure devices (relief valves) used 

in assemblies will comply to EN 12186 and EN 12279 

standards.

relief Valves

Figure 1.

  Relief Valves V/50, V/60 Series and Type V/20-2

Содержание Tartarini V Series

Страница 1: ...ontact your local sales agent SEP statement Emerson Process Management declares this product V 50 and V 20 2 conforms to Pressure Equipment Directive PED 97 23 EC Article 3 section 3 and was designed and manufactured in accordance with sound engineering practice SEP Per Article 3 section 3 this SEP product must not bear the CE marking Product Description The V Series are spring loaded automatic ty...

Страница 2: ... not be exceeded Maximum Allowable Pressure V 50 Series 4 bar V 60 Series 2 5 bar Type V 20 2 100 bar Outlet Set Pressure Ranges V 50 Series 0 025 2 bar V 60 Series 0 025 2 bar Type V 20 2 1 5 40 bar Minimum Maximum Allowable Temperature TS See label Temperature Standard Version Working 10 to 60 C Low Temperature Version Working 20 to 60 C Materials V 50 and V 60 Series Body cover Aluminium Seat B...

Страница 3: ...work 5m sec In any case provisions of Directive 1999 92 EC and 89 655 EC shall be enforced by gas pressure regulating measuring station installation s end user with a view to preventing and providing protection against explosions technical and or organizational measures appropriate to the nature of the operation shall be taken e g filling exhausting of fuel gas of internal volume of the isolated p...

Страница 4: ... adjusting the compression of spring M through the appropriate ring G It is recommended that relief valve be set at a value at least 15 higher than the operating pressure of the station Dimensions and Weights V 50 and V 60 Series Table 2 V Series Dimensions mm TYPE V 50 SERIES V 60 SERIES A 236 258 B 164 198 C 43 70 D 95 110 Weight Kg 1 3 1 9 Ø B D A C Figure 5 V 50 and V 60 Series Dimensions Type...

Страница 5: ...injury or damage provide piping or tubing to vent the gas to a safe well ventilated area in accordance also with international and applicable codes and regulations In particular when venting a hazardous gas the piping or tubing should be located far enough away from any buildings or windows so to not create a further hazard and the vent opening should be protected against anything that could clog ...

Страница 6: ... CE marking shall be covered also after every subsequent reassembly at installation site in order to ensure that the equipment will be safe throughout its intended life Before proceeding with any maintenance work shutoff the gas upstream and downstream from the valve also ensure that there is no gas under pressure inside the body by loosening the upstream and downstream connections V 50 Series See...

Страница 7: ...aging or any damage Troubleshooting Table 3 General Troubleshooting for V Series Relief Valves SYMPTOMS cause ACTIONS The valve does not open Lack of incoming gas Check the station feeding Valve diaphragm is broken V 50 and V 60 Series only To be replaced Valve setting is higher than required Check valve setting Pad is stuck to seat Perform complete valve maintenance The valve is not sealed proper...

Страница 8: ...on 1 Cap 2 Nut 3 Spring 4 Nut 5 Nut 6 Washer 7 Disk 8 Plate 9 Diaphragm 10 Screw 11 Pad unit 12 Seat 13 O ring 14 Pad retainer 15 Body 16 Seeger 17 Net 18 Label 19 Cover 20 Adjusting nut 21 Threaded stem 22 Reduction ring Type V 20 2 Relief Valve See Figure 9 Key Description 1 Body 2 Adjusting nut 4 Pad holder 5 Nut 6 Pad 7 Pad retainer 8 Spring 9 Outlet connection Rubber parts marked with are sup...

Страница 9: ...V Series 9 1 2 4 21 3 5 6 18 19 20 7 8 9 10 11 12 13 14 15 16 17 TYPE V 50 TYPE V 51 DETAIL 8 9 TYPE V 52 DETAIL 8 9 22 10 15 Figure 7 V 50 Series Relief Valve LM 518 1 Schematic Assemblies ...

Страница 10: ...V Series 10 LM 1160 Figure 8 V 60 Series Relief Valve 7 8 9 10 22 TYPE V 62 DETAIL 9 TYPE V 61 DETAIL 1 2 3 4 5 6 7 9 10 11 12 13 14 15 16 17 8 18 19 20 21 TYPE V 60 ...

Страница 11: ...V Series 11 Figure 9 Type V 20 2 Relief Valve LM 643 1 2 4 5 6 7 8 9 ...

Страница 12: ...ters McKinney Texas 75070 USA Tel 1 800 558 5853 Outside U S 1 972 548 3574 Asia Pacific Shanghai 201206 China Tel 86 21 2892 9000 Europe Bologna 40013 Italy Tel 39 051 419 0611 Middle East and Africa Dubai United Arab Emirates Tel 971 4811 8100 For further information visit www emersonprocess com regulators Natural Gas Technologies Emerson Process Management Regulator Technologies Inc USA Headqua...

Отзывы: