from vehicular traffic and positioned 

so that water, ice and other foreign 

materials cannot enter the spring 

case through the vent. Avoid placing 

the regulator beneath eaves or 

downspouts and be sure it is above 

the probable snow level.

overpressure Protection

The recommended pressure limitations are 

stamped on the regulator nameplate. Some type of 

overpressure protection is needed if the actual inlet 

pressure exceeds the maximum operating outlet 

pressure rating. Overpressure protection should 

also be provided if the regulator inlet pressure 

is greater than the safe working pressure of the 

downstream equipment.
Regulator operation below the maximum pressure 

limitations does not preclude the possibility of 

damage from external sources or debris in the line. 

The regulator should be inspected for damage after 

any overpressure condition.

startup

The regulator is factory set at approximately 

the midpoint of the spring range or the pressure 

requested, so an initial adjustment may be required 

to give the desired results. With proper installation 

completed and relief valves properly adjusted, 

slowly open the upstream and downstream 

shutoff valves.

Adjustment

The adjustment of setpoint is performed using 

the pilot adjusting screw. To change the outlet 

pressure, loosen the jam nut and turn the adjusting 

screw clockwise to increase outlet pressure or 

counterclockwise to decrease it. Monitor the outlet 

pressure with a test gauge during the adjustment. 

Tighten the jam nut to maintain the desired setting.

If the regulator vents fluid or a 

leak develops in the system, it 

indicates that service is required. 

Failure to take the regulator out of 

service immediately may create a 

hazardous condition.
Personal injury, equipment damage 

or leakage due to escaping fluid 

or bursting of pressure containing 

parts may result if this regulator is 

overpressured or is installed where 

service conditions could exceed the 

limits given in the Specifications 

section or where conditions exceed 

any ratings of the adjacent piping or 

piping connections.
to avoid such injury or damage, 

provide pressure-relieving or 

pressure-limiting devices (as required 

by the appropriate code, regulation 

or standard) to prevent service 

conditions from exceeding limits.
Additionally, physical damage to the 

regulator could result in personal 

injury and property damage due to 

escaping fluid. To avoid such injury 

and damage, install the regulator in a 

safe location.

Clean out all pipelines before installation of the 

regulator and check to be sure the regulator has 

not been damaged or has collected foreign material 

during shipping. For flanged bodies, use suitable line 

gaskets and approved piping and bolting practices. 

Install the regulator in any position desired, unless 

otherwise specified, but be sure flow through the 

body is in the direction indicated by the arrow on 

the body.

Note

It is important that the regulator be 

installed so that the vent hole in the 

spring case is unobstructed at all 

times. For outdoor installations, the 

regulator should be located away 

Table 1.

 Outlet Pressure Ranges

tYPE

outLEt PrEssurE rANGE

AC (ACCurACY CLAss)

PILot CoNtroL sPrING 

INForMAtIoN

bar

psig

spring Color

PRX/120

PRX/125

PRX/131

1.0 to 1.8

1.6 to 3.0

2.8 to 5.5

5.0 to 8.5

14.5 to 26

23 to 44

41 to 80

73 to 123

2.5%

2.5%

2.5%

2.5%

Yellow

Green

Blue

Black

8.0 to 14.5

14.0 to 23.0

22.0 to 30.0

116 to 210

203 to 334

319 to 435

1%

1% 

1%

Silver

Gold

Aluminum

PRX/120-AP

PRX/125-AP

30.0 to 80.0

435 to 1160

1%

Clear

Содержание TARTARINI FL Series

Страница 1: ...ential Pressure continued 2 Full Open DN 25 to 100 NPS 1 to 4 1 00 bar d 14 5 psid DN 150 and 200 NPS 6 and 8 0 50 bar d 7 3 psid DN 250 NPS 10 0 6 bar d 8 7 psid Outlet Pressure Ranges See Table 1 Pressure Registration External Temperature Capabilities 1 3 Nitrile NBR Fluorocarbon FKM or Polyurethane PU Disk 20 to 60 C 4 to 140 F Nitrile NBR or Polyurethane PU Disk 29 to 60 C 20 to 140 F 5 Approx...

Страница 2: ...regulator out of service immediately may create a hazardous condition Personal injury equipment damage or leakage due to escaping fluid or bursting of pressure containing parts may result if this regulator is overpressured or is installed where service conditions could exceed the limits given in the Specifications section or where conditions exceed any ratings of the adjacent piping or piping conn...

Страница 3: ...required DN 200 NPS 8 16 required DN 250 NPS 10 20 required 28 O ring 29 Nameplate 30 Nameplate Sticker 31 Drive Screw 4 required 32 Flow Arrow 33 Spring Collet not available for DN 250 NPS 10 34 Indicator Stem not available for DN 250 NPS 10 35 O ring 36 Indicator Fitting 37A O ring 37B O ring 38 Indicator Bushing 39 Indicator Scale 40 Indicator Cover not available for DN 250 NPS 10 43 Type SR Si...

Страница 4: ... Cover O ring 19 Orifice 20 Nut 21 Lower Cover 22 Pad Holder 23 Stem 24 Nameplate 25 Stem O ring 26 Upper Diaphragm Nut 27 Damper Adjusting Screw with Hole 28 Restrictor Damper O ring 29 Damper Restrictor Plate Types PRX 120 and PRX 120 AP Types PRX 125 and PRX 125 AP 30 Ring Nut 31 Nameplate Screw 32 Restrictor Adjusting Screw with Hole 33 Plug Types PRX 125 and PRX 125 AP only 34 Plug Types PRX ...

Страница 5: ...5 Type FL DN 200 NPS 8 Figure 1 Type FL Main Valve Assembly LM 1403 40 34 38 36 66 37B 35 33 31 32 31 30 29 28 65 27 26 1 2 3 2 2 3 2 6 4 2 3 5 2 8 9 10 11 12 13 14 15 16 18 59 22 23 24 59 64 ...

Страница 6: ...21 20 21 48 Figure 2 Polyurethane PU Main Valve Assembly DN 25 AND 50 NPS 1 AND 2 without silencer DN 80 TO 150 NPS 3 TO 6 without silencer DN 200 TO 250 NPS 8 TO 10 without silencer DN 80 TO 150 NPS 3 TO 6 with Type sr DN 25 AND 50 NPS 1 AND 2 with Type sr ersa03388 ersa03389 ersa03393 ersa03394 ersa03396 ...

Страница 7: ...Figure 3 Type SRS Assembly 211 210 206 209 208 206 207 206 200 201 202 203 204 205 23 24 200 spacer details for DN 150 TO 300 NPS 6 TO 12 DN 25 TO 150 NPS 1 TO 6 spacer details for sizes smaller than DN 150 NPS 6 ...

Страница 8: ...8 Type FL 57 54 53 55 L PORT DN 25 TO 50 NPS 1 TO 2 A PORT TYPE PRX 120 B PORT TYPE SA 2 50 56 52 GE46220_A Figure 4 Type FL Single Pilot Mounting Assembly ...

Страница 9: ... A 18 11 26 28 34 29 31 28 34 33 33 28 31 29 28 34 34 18 22 19 14 17 16 18 14 13 13 15 25 S S L L B B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 14 18 19 13 11 20 10 11 21 22 23 24 18 11 26 25 Figure 5 PRX Series Pilot Assembly Type PRX 131 or PRX 131 AP assembly Section a a Type PRX 120 or PRX 125 ...

Страница 10: ...egulators Emerson Process Management Regulator Technologies Inc USA Headquarters McKinney Texas 75070 USA Tel 1 800 558 5853 Outside U S 1 972 548 3574 Asia Pacific Shanghai 201206 China Tel 86 21 2892 9000 Europe Bologna 40013 Italy Tel 39 051 419 0611 Middle East and Africa Dubai United Arab Emirates Tel 971 4811 8100 Natural Gas Technologies Emerson Process Management Regulator Technologies Inc...

Отзывы: