NOTICE
INADEQUATE RACEWAY ELECTRICAL CONTINUITY
•
Install an insulated grounding conductor inside a metallic raceway
when the raceway is used as an additional
grounding conductor. Size the conductor in accordance with all applicable codes.
• Maintain adequate electrical continuity at all raceway connections.
•
Do not use isolating bushings to interrupt a metallic raceway run.
•
Do not use a separate isolated ground for the surge protective device.
•
Verify proper equipment connections to the grounding system.
•
Verify ground grid continuity by inspections and testing as part of a comprehensive electrical maintenance
program.
Failure to follow these instructions can result in equipment damage.
Wiring and Installation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E,
NOM-029-STPS or CSA Z462.
•
This equipment must only be installed and serviced by qualified electrical personnel.
•
Turn off all power supplying this equipment before working on or inside equipment.
•
Always use a properly rated voltage sensing device to confirm power is off.
•
Replace all devices, doors and covers before turning on power to this equipment.
•
This equipment must be effectively grounded per all applicable codes. Use an equipment-grounding conductor to
connect this equipment to the power system ground.
•
Confirm the surge protective device voltage rating on the module or nameplate label is not less than the operat
-
ing voltage.
Failure to follow these instructions will result in death or serious injury.
Parts List
1 - SPD50K suppressor including 3' (~1m) conductors
1 - 3/4” conduit nut
1 - L bracket mounting kit; includes two pan head screws
1 - Instructions