SDU AC-B Series
A272-353 Rev. 1 2/2021
6 |
P a g e
8.
COMM PORT: Communication card slot.
COMM CARDS: SDUCFRELAYCARD and Active communication cards can be purchased separately.
The UPS can detect the presence of a COMM CARD and identify what kind of COMM CARD is
inserted. USB communication will have precedence over COMM CARDS.
For more details Please reference Documents within the SDU AC B Series webpage within
.
9.
REMOTE ON/OFF TERMINALS:
Use a switch to remotely toggle ON/OFF state. Non-Polarized terminals.
No external voltage is required
. We recommend using stranded UTP (Unshielded Twisted Pair) wire for
connections.
Remote ON/OFF is grounded to the UPS internal signal ground so it should be isolated from
the chassis ground to prevent any ground potentials that may cause a unit malfunction or
damage. In addition, isolate the Remote ON/OFF wiring away from high current, high
voltage, and high frequency components to prevent any magnetically coupled noise on the
Remote On/Off connections.
Screw
M3.0; Current rating = 35 A, AC 600
V
Insulation Withstands Volts
A 2000 V min.
Preferred AWG
8
–
18 AWG
Screw Torque
9 lb-in (101.68 N-cm)
Screw Terminals Description
Catalog Number
Dimensions in Inches (Millimeters)
H
W
D
SDU AC - B SERIES
5.0(126.7)
11.0(279.5)
5.3(135.2)
Figure 3: Product Dimensions
!