When the Condensate Switch Monitor is connected to the Data Hub the green light will be on, as 

shown in Figure A. If the monitor’s green LED does not illuminate and the Data Hub is powered 

on, unplug the 3-pin connector, flip over and reinsert.

Proper connection to the condensate switch may be confirmed by momentarily opening the 

switch and observing that the red light comes on, as seen in Figure B. (24 volt system power 

must be on and the control wire being interrupted must be active for this step.) If the red light 

does not indicate when the switch is open, please verify that the switch is operating correctly.

In the event of a condensate switch opening the red light will illuminate and the Sensi Predict 

system will detect an open status. Sensi Predict technicians will not trigger a homeowner alert 

unless an actual condensate event is diagnosed. When the condensate switch closes (after 

removing the clog and draining the water) the red light will go out.

SENSOR LED LIGHTS

fig.a

fig.b

SENSOR LED LIGHT INDICATORS

0037-7658001

The Sensi Predict PRO Portal can be accessed at sensipredictpro.com 

For login support, contact your office administrator. 

For support within the PRO Portal, call 1-877-424-1715.