This guide describes installation and activation of the Sensi Predict
™
Condensate Switch
Monitor accessory. The accessory provides indication of system shutdown by condensate level
switches responding to excessive water levels. One or more switches may be monitored.
To install, connect the free wires of the condensate switch monitor to either end of the
condensate switch chain as shown below. Plug the connector into one of the accessory ports
of the Sensi Predict Data Hub and ensure that the red stripe on the 3-pin connector side of the
wire is facing up, as illustrated below. See back for validation procedure.
CONDENSATE SWITCH MONITOR CONNECTIONS
BEFORE INSTALL
0037-7658001
NOTE: Please verify that the condensate switch is rated
to control the connected load.
NOTE: The condensate switch monitor MUST be wired
in parallel
Ensure that the red stripe on the 3-pin connector side
of the wire is facing up, as shown above
CONDENSATE
SWITCH WIRES
R,C, OR Y
CONTROL WIRE
INDOOR DEVICE
R,C, OR Y
CONTROL WIRE
CONDENSATE
SWITCH MONITOR
TO CONDENSATE SWITCH(S)
CONDENSATE
SWITCH WIRES
R,C, OR Y
CONTROL WIRE
R,C, OR Y
CONTROL WIRE
TO CONDENSATE SWITCH(S)
CONDENSATE SWITCH MONITOR INSTALLATION GUIDE
WARNING
ELECTRICAL SHOCK/FIRE HAZARD
• Installer must be qualified technician
• Connect only to a 24 volt class 2 circuit
• Follow all local and national codes and ordinances
• Ensure proper operation of HVAC system, following manufacturer’s instructions