This guide describes installation and activation of the Sensi Predict

 Condensate Switch 

Monitor accessory. The accessory provides indication of system shutdown by condensate level 

switches responding to excessive water levels. One or more switches may be monitored.

To install, connect the free wires of the condensate switch monitor to either end of the 

condensate switch chain as shown below. Plug the connector into one of the accessory ports 

of the Sensi Predict Data Hub and ensure that the red stripe on the 3-pin connector side of the 

wire is facing up, as illustrated below. See back for validation procedure.

CONDENSATE SWITCH MONITOR CONNECTIONS

BEFORE INSTALL

0037-7658001

NOTE: Please verify that the condensate switch is rated 

to control the connected load.

NOTE: The condensate switch monitor MUST be wired 

in parallel 

Ensure that the red stripe on the 3-pin connector side 

of the wire is facing up, as shown above

CONDENSATE

SWITCH WIRES

R,C, OR Y

CONTROL WIRE

INDOOR DEVICE

R,C, OR Y

CONTROL WIRE

CONDENSATE

SWITCH MONITOR

TO CONDENSATE SWITCH(S)

CONDENSATE

SWITCH WIRES

R,C, OR Y

CONTROL WIRE

R,C, OR Y

CONTROL WIRE

TO CONDENSATE SWITCH(S)

CONDENSATE SWITCH MONITOR INSTALLATION GUIDE

WARNING

ELECTRICAL SHOCK/FIRE HAZARD

• Installer must be qualified technician

• Connect only to a 24 volt class 2 circuit

• Follow all local and national codes and ordinances

•  Ensure proper operation of HVAC system, following manufacturer’s instructions

The Sensi Predict PRO Portal can be accessed at sensipredictpro.com 

For login support, contact your office administrator. 

For support within the PRO Portal, call 1-877-424-1715.