Reference Manual
00809-0100-4021, Rev GC
Section 3: HART commissioning
April 2014
3.16.2
LCD display
The LCD displays abbreviated diagnostic messages for troubleshooting the transmitter. To
accommodate two word messages, the display alternates between the first and second word.
Some diagnostic messages have a higher priority than others, so messages appear according to
priority, with normal operating messages appearing last. Messages on the
Process Variable
line
refer to general device conditions, while messages on the
Process Variable Unit
line refer to
specific causes for these conditions. A description of each diagnostic message follows.
Table 3-4. LCD Display Error Warning Descriptions
Message
Description
[BLANK]
If the meter does not appear to function, make sure the transmitter is configured for the meter
option you desire. The meter will not function if the LCD Display option is set to Not Used.
FAIL -or- HDWR FAIL
This message indicates one of several conditions including:
The transmitter has experienced an electronics module failure.
The transmitter self-test has failed.
If diagnostics indicate a failure of the electronics module, replace the electronics module with a
new one. Contact the nearest Emerson Process Management Field Service Center if necessary.
SNSR 1 FAIL -or-
SNSR 2 FAIL
The transmitter has detected an open or shorted sensor condition. The sensor(s) might be
disconnected, connected improperly, or malfunctioning. Check the sensor connections and
sensor continuity.
SNSR 1 SAT -or-
SNSR 2 SAT
The temperature sensed by the transmitter exceeds the sensor limits for this particular sensor
type.
HOUSG SAT
The transmitter operating temperature limits (–40 to 185 °F (40 to 85 °C)) have been exceeded.
LOOP FIXED
During a loop test or a 4–20 mA output trim, the analog output defaults to a fixed value. The
Process Variable
line of the display alternates between the amount of current selected in
milliamperes and “WARN.” The
Process Variable Unit
line toggles between “LOOP,” “FIXED,” and
the amount of current selected in milliamperes.
OFLOW
The location of the decimal point, as configured in the meter setup, is not compatible with the
value to be displayed by the meter. For example, if the meter is measuring a process temperature
greater than 9.9999 degrees, and the meter decimal point is set to 4 digit precision, the meter will
display an “OFLOW” message because it is only capable of displaying a maximum value of 9.9999
when set to 4 digit precision.
HOT BU
Hot Backup is enabled and Sensor 1 has failed. This message is displayed on the
Process Variable
line and is always accompanied by a more descriptive message on the
Process Variable Unit
line. In
the case of a Sensor 1 failure with Hot Backup enabled, for example, the
Process Variable
line
displays “HOT BU,” and the
Process Variable Unit
line alternates between “SNSR 1” and “FAIL.”
WARN DRIFT ALERT
Drift Alert warning is enabled and the difference between Sensor 1 and Sensor 2 has exceeded the
user-specified limit. One of the sensors may be malfunctioning. The
Process Variable
line displays
“WARN” and the
Process Variable Unit
line alternates between “DRIFT” and “ALERT.”
ALARM DRIFT ALERT
The analog output is in alarm. Drift Alert alarm is enabled and the difference between Sensor 1
and Sensor 2 has exceeded the user-specified limit. The transmitter is still operating, but one of
the sensors may be malfunctioning. The
Process Variable
line displays “ALARM” and the
Process
Variable Unit
line alternates between “DRIFT” and “ALERT.”
ALARM
The digital and analog outputs are in alarm. Possible causes of this condition include, but are not
limited to, an electronics failure or an open sensor. This message is displayed on the
Process
Variable
line and is always accompanied by a more descriptive message on the
Process Variable
Unit
line. In the case of a Sensor 1 failure, for example, the
Process Variable
line displays “ALARM,”
and the
Process Variable Unit
line alternates between “SNSR 1” and “FAIL.”
WARN
The transmitter is still operating, but something is not correct. Possible causes of this condition
include, but are not limited to, an out-of-range sensor, a fixed loop, or an open sensor condition.
In the case of a Sensor 2 failure with Hot Backup enabled, the
Process Variable
line displays
“WARN,” and the
Process Variable Unit
line alternates between “SNSR 2” and “RANGE.”
Содержание Rosemount
Страница 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Страница 2: ......
Страница 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Страница 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Страница 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Страница 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Страница 233: ...227 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 234: ...228 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 235: ...229 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 237: ...231 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 238: ...232 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 244: ...238 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Страница 251: ......