Reference Manual
00809-0100-4045, Rev AB
Operation and Maintenance
March 2016
Operation and Maintenance
4.4
Replacing the battery
Procedure to replace the battery:
1.
Remove enclosure cover.
2.
Switch the device “OFF”.
3.
Loosen the screw holding the electronics assembly to the enclosure.
Note
Use caution as the electronics assembly is connected to the pressure sensor via a cable. Take
care not to over stretch this cable as this could damage the device.
4.
Release battery connection from electronics board.
5.
Loosen the two screws on the battery holder and slide the battery holder to the
left.
Note
The screws holding down the electronics board do not need to be removed, just loosened.
Take care not to let the battery fall out of the enclosure.
6.
Remove battery from enclosure.
7.
Installation of new b attery is the reverse of the removal.
The Rosemount Wireless Pressure Gauge shall be used only with the battery
(00G45-9000-0001) supplied by Rosemount. This battery has been officially tested
with the device as required by the I.S. standards during the assessment of the
Rosemount Wireless Pressure Gauge.
The battery is not replaceable in a hazardous location.
Dispose of battery in accordance with local and national jurisdictions.
Содержание Rosemount WPG
Страница 2: ......
Страница 10: ...4 Reference Manual 00809 0100 4045 Rev AB Introduction March 2016 Introduction ...
Страница 32: ...26 Reference Manual 00809 0100 4045 Rev AB Configuration March 2016 Configuration ...
Страница 40: ...34 Reference Manual 00809 0100 4045 Rev AB Operation and Maintenance March 2016 Operation and Maintenance ...
Страница 46: ...40 Reference Manual 00809 0100 4045 Rev AB Troubleshooting March 2016 Troubleshooting ...
Страница 69: ......