Time constant
4 seconds maximum required to reach 63.2 percent sensor response in
water flowing at 3 ft/s (0.91 m/s).
Self heating
18 mW minimum power dissipation required to cause a 1 °C (1.8 °F)
temperature measurement error in water flowing at 3 ft/s.
Insulation resistance
500
×
10
6
ohms minimum insulation resistance when measured at 500 Vdc
at room temperature (20 °C [68 °F]).
6.1.2
Environmental specifications
Humidity limits
Lead seal is capable of withstanding 100 percent relative humidity.
Vibration limits
Standard single- and dual-element sensors
±0.03 percent maximum ice-point resistance shift due to 30 minutes of 21 g
peak vibration from 5 to 350 Hz continuous sweep at 20 °C (68 °F) for
unsupported stem length of less than 5.5-in. (140 mm).
Quality assurance
Each sensor is subjected to a resistance accuracy test at 0 °C and an
insulation resistance test.
Enclosure ratings
When installed properly, Rosemount Series 78 Sensors are suitable for
indoor and outdoor NEMA 4X and CSA Enclosure Type 4X installations.
6.1.3
Physical specifications
Sheath material
Single and dual-element, 316 SST
Lead wires
Single and dual-element, PTFE-insulated, nickel-coated, 22-gauge stranded
copper wire.
Identification data
The model and serial numbers and up to six lines of permanent tagging
information are etched on each sensor adapter. Stainless steel tags are
available upon request.
March 2021
Quick Start Guide
Quick Start Guide
13
Содержание Rosemount Volume 1
Страница 1: ...Quick Start Guide 00825 0300 2654 Rev GB March 2021 Rosemount Volume 1 Sensor Assembly ...
Страница 28: ...Quick Start Guide March 2021 28 Emerson com Rosemount ...
Страница 30: ...Quick Start Guide March 2021 30 Emerson com Rosemount ...
Страница 31: ...March 2021 Quick Start Guide Quick Start Guide 31 ...