Section 7: Foundation
Fieldbus
April 2017
Instruction Manual
IM-106-880C, OI
12
8
Troubleshootin
g
7.11.17
Troubleshooting
Refer to
to troubleshoot any problems that you encounter.
Table 7-26 Troubleshooting
Mode will not leave
OOS
Process and/or block
alarms will not work
Value of output does
not make sense
1.
Target mode not set
2.
Configuration error
3.
Resource block
4.
Schedule
1.
Features
2.
Notification
3.
Status Options
1.
Linearization Type
2.
Scaling
1.
Set target mode to something other than OOS.
2.
BLOCK_ERR will show the configuration error bit set. The
following are parameters that must be set before the block is
allowed out of OOS:
a.
CHANNEL must be set to a valid value and cannot be left at
initial value of 0.
b.
XD_SCALE.UNITS_INDX must match the units in the
transducer block channel value.
c.
L_TYPE must be set to Direct, Indirect, or Indirect Square Root
and cannot be left at initial value of 0.
3.
The actual mode of the Resource block is OOS. See Resource
Block Diagnostics for corrective action.
4.
Block is not scheduled and therefore cannot execute to go to
Target Mode. Schedule the block to execute.
1.
FEATURES_SEL does not have Alerts enabled. Enable the Alerts
bit.
2.
LIM_NOTIFY is not high enough. Set equal to MAX_NOTIFY.
3.
STATUS_OPTS has Propagate Fault Forward bit set. This should
be cleared to cause an alarm to occur.
1.
Does not make L_TYPE must be set to Direct, Indirect, or
Indirect Square Root and cannot be left at initial value 0.
2.
Scaling parameters are set incorrectly:
a.
XD_SCALE.EU0 and EU100 should match that of the
transducer block channel value.
b.
OUT_SCALE.EU0 and EU100 are not set properly.
Cannot Set HI_LIMIT,
HI_HI_LIMIT
LO_LIMIT, or
LO_LO_LIMIT
Values
1.
Scaling
1. Limit values are outside the OUT_SCALE.EU0 and
OUT_SCALE.EU100 values. Change OUT_SCALE or set values
within range.
Symptom
Possible Cause
Corrective Action
Содержание Rosemount OCX 8800
Страница 2: ......
Страница 41: ...Instruction Manual IM 106 880C OI Section 2 Installation April 2017 Section contents 17 ...
Страница 192: ...Section 7 Foundation Fieldbus April 2017 Instruction Manual IM 106 880C OI 16 6 About AMS and DeltaV Software ...
Страница 205: ...Alarm Relay Events April 2017 Instruction Manual IM 106 880C OI 17 8 Alarm Relay Events ...
Страница 251: ...Replace Tube Fittings April 2017 Instruction Manual IM 106 880C OI 22 4 Install Tube Fittings ...
Страница 259: ...Section 10 Replacement Parts April 2017 Instruction Manual IM 106 880C OI 23 2 O2 Cell and Heater Strut Assembly ...
Страница 261: ...Instruction Manual IM 106 880C OI Safety Data April 2017 Appendix contents 233 ...
Страница 263: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 235 ...
Страница 267: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 239 ...
Страница 271: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 243 ...
Страница 273: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 245 ...
Страница 275: ...Instruction Manual Safety Data IM 106 880C OI April 2017 IMPORTANT Safety Instructions 247 ...
Страница 277: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 249 ...
Страница 279: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 251 ...
Страница 298: ...SPA with HART Alarm April 2017 Instruction Manual IM 106 880C OI 27 2 Configuration Calibratio n ...
Страница 300: ...Instruction Manual IM 106 880C OI Index April 2017 Manual index 27 4 ...
Страница 304: ...Index April 2017 Instruction Manual IM 106 880C OI 27 8 Manual index ...
Страница 305: ......