1
Introduction
To comply with local standards and jurisdictional authorities, perform end-to-end loop
testing of fire protection alarm systems, including detectors, periodically. Many safety
authorities and plant managers of high value/high risk assets and facilities insist on
quarterly end-to-end testing of their entire fire protection systems using an external flame
simulator.
Rosemount Flame Simulators emit electromagnetic radiation in a unique sequential
pattern corresponding to and recognizable as fire by the specific Rosemount 975 Flame
Detector. This allows the detector to be tested under real fire conditions without the
associated risk of an open flame.
Rosemount Flame Simulators are ATEX certified EExd for use in Zone 1 and Zone 2
hazardous areas and are powered by rechargeable lithium ion batteries. When fully
charged, the flame simulator will operate for at least 100 tests without recharging.
The Rosemount Flame Simulator is the only non-hazardous and safe method to test the
flame detector's sensors, internal electronics, alarm activation software, cleanliness of the
viewing window/lens, wiring integrity, actual relay activation, and proper functionality of
any other outputs used (mA, RS-485, or HART
®
).
1.1
Flame simulator compatibility with flame
detector models
The Rosemount FS-UVIR-975 Flame Simulator is compatible with the following:
Table 1-1: Flame simulator compatibility
Simulator
Part number
Compatible with
Ultraviolet infrared flame simulator
FS-UVIR-975
Rosemount 975UR and
975UF
1.2
Features and benefits
•
Used for maintenance and testing of flame detectors.
•
Can activate the flame detector from a distance of 23 ft (7 m).
•
Includes rechargeable battery.
•
Operates at least 100 tests before the battery must be recharged.
1.3
Principles of operation
The simulator includes a reflector which accumulates the infrared energy and directs it
towards the detector. The Rosemount FS-UVIR-975 also includes a sight in order to point
the simulator to the center of the flame detector.
Reference Manual
Introduction
00809-0800-4975
May 2022
Rosemount FS-UVIR-975
7
Содержание Rosemount FS-UVIR-975
Страница 1: ...Reference Manual 00809 0800 4975 Rev DD May 2022 Rosemount FS UVIR 975 ...
Страница 4: ...4 ...
Страница 6: ...Contents Reference Manual May 2022 00809 0800 4975 6 Emerson com Rosemount ...
Страница 14: ...Operation Reference Manual May 2022 00809 0800 4975 14 Emerson com Rosemount ...
Страница 18: ...Maintenance Reference Manual May 2022 00809 0800 4975 18 Emerson com Rosemount ...
Страница 20: ...Ordering information Reference Manual May 2022 00809 0800 4975 20 Emerson com Rosemount ...
Страница 26: ...Product certifications Reference Manual May 2022 00809 0800 4975 26 Emerson com Rosemount ...