9.10
Simulating temperature
9.10.1
General information about simulating temperature
The transmitter accepts a Pt100 resistance temperature device. The Pt100 resistance
temperature device is a three-wire configuration.
Figure 9-4: Three-Wire RTD Configuration
A. Resistance temperature device
B. Resistance temperature device in
C. Resistance temperature device sense
D. Resistance temperature device return
Although only two wires are required to connect the resistance temperature device to the
transmitter, using a third (and sometimes fourth) wire allows the transmitter to correct for
the resistance of the lead wires and for changes in the lead wire resistance with
temperature.
9.10.2
Simulate temperature
To simulate the temperature input, wire a decade box to the transmitter as shown in
Troubleshoot