2.5
Installing cables
When installing cables for the flame detector, consider the following:
•
Ensure all cables to the detector are well shielded in order to comply with EMC
requirements.
•
Ground the detector to the nearest ground point (not more than 9.8 ft. (3 m) from the
flame detector).
•
Install the detector with the cable entries and conduit pointed downwards.
2.5.1
Installing conduit
The conduit used for the cabling must comply with the following:
•
To avoid water condensation in the detector, install the detector with the conduits that
include drain holes pointed downwards.
•
When using the optional tilt mount, use flexible conduits for the last portion
connecting to the detector.
•
For installation in atmospheres as defined in group B of the NFPA 72E, seal the conduit
inlets.
•
When pulling the cables through the conduits, ensure that they are not tangled or
stressed. Extend the cables about 12 in. (30 cm) beyond the detector location to
accommodate wiring after installation.
•
After pulling the conductor cables through the conduits, perform a continuity test.
2.6
Installing the tilt mount (PN 00975-9000-0001)
The tilt mount (PN 00975-9000-0001) enables the detector to rotate up to 60 degrees in
all directions.
shows the detector mounted on the tilt mount.
Installing the detector
Reference Manual
August 2019
00809-0100-4975
28
Emerson.com/Rosemount
Содержание Rosemount 975MR
Страница 38: ...Installing the detector Reference Manual August 2019 00809 0100 4975 38 Emerson com Rosemount ...
Страница 46: ...Maintenance and troubleshooting Reference Manual August 2019 00809 0100 4975 46 Emerson com Rosemount ...
Страница 52: ...Specifications and reference data Reference Manual August 2019 00809 0100 4975 52 Emerson com Rosemount ...
Страница 60: ...RS 485 communication network Reference Manual August 2019 00809 0100 4975 60 Emerson com Rosemount ...
Страница 67: ...Figure D 4 Duct Mount Reference Manual Accessories 00809 0100 4975 August 2019 Rosemount 975MR 67 ...
Страница 70: ...Accessories Reference Manual August 2019 00809 0100 4975 70 Emerson com Rosemount ...