Only access the wiring compartment to wire or remove the detector or access RS-485
terminals for maintenance.
•
Disconnect or disable external devices, such as automatic extinguishing systems,
before carrying out any maintenance.
3.2.1
Factory default function settings
lists the default function configurations supplied with the detector.
Table 3-1: Factory Default Function Settings
Function
Value
Notes
Sensitivity
30
Alarm delay
A
Antiflare
Alarm latch
No
Auxiliary relay
No
In output configurations 1A,
2A, and 3A, the auxiliary relay is
not available. This function is
not used.
Automatic built-in test (BIT)
Yes
Alarm built-in-test
No
Auxiliary built-in test
No
In output configurations 1A,
2A, and 3A, the auxiliary relay is
not available. This function is
not used.
Heated optics
Auto
Heat on
41 °F (5 °C)
The detector starts heating the
window for any temperature
below this value.
In order to change the default function, use:
•
USB RS-485 harness kit PN 00975-9000-001
•
HART
®
protocol. Refer to the
Rosemount 975 Flame Detector HART Communication
for instructions.
3.3
Testing procedures
This section describes the proof testing procedure for proper operation of the detector.
Test the detector using the manual built-in test (BIT) or the flame simulator.
The detector performs the internal test continuously and the automatic built-in test every
fifteen minutes; for more details, refer to
.
Operating the detector
Reference Manual
June 2021
00809-0100-4976
44
Emerson.com/Rosemount
Legacy
Содержание Rosemount 975HR
Страница 28: ...Introduction Reference Manual June 2021 00809 0100 4976 28 Emerson com Rosemount L e g a c y ...
Страница 42: ...Installing the detector Reference Manual June 2021 00809 0100 4976 42 Emerson com Rosemount L e g a c y ...
Страница 66: ...RS 485 communication network Reference Manual June 2021 00809 0100 4976 66 Emerson com Rosemount L e g a c y ...
Страница 78: ...SIL 2 features Reference Manual June 2021 00809 0100 4976 78 Emerson com Rosemount L e g a c y ...